AIR CONDITIONING SYSTEM (for Manual Air Conditioning System), Diagnostic DTC:B1412/12

Click here
Click here
DTC Code DTC Name
B1412/12 Ambient Temperature Sensor Circuit
Click here

DESCRIPTION

The ambient temperature sensor is installed in front of the condenser.

The air conditioning amplifier applies a voltage (5 V) to the ambient temperature sensor and reads voltage changes as changes in the resistance of the ambient temperature sensor.

DTC No. DTC Detection Condition Trouble Area
B1412/12 Open or short in ambient temperature sensor circuit
  • Ambient temperature sensor

  • Wire harness between ambient temperature sensor and Air conditioning amplifier

  • Air conditioning amplifier

Click here

WIRING DIAGRAM

Click here

INSPECTION PROCEDURE

Click here

PROCEDURE


  1. Click here

    READ VALUE USING INTELLIGENT TESTER (AMBI TEMP SENS)


    1. Connect the intelligent tester to the DLC3.

    2. Turn the ignition switch on (IG) and turn the intelligent tester main switch on.

    3. Select the item below in the Data List, and read the value displayed on the intelligent tester.

      Table 1. Data List / Air Conditioner:
      Tester Display Measurement Item/Range Normal Condition Diagnostic Note
      Ambi Temp Sens

      Ambient temperature sensor /

      Min.: -23.3°C (-9.94°F)

      Max.: 65.95°C (150.71°F)

      Actual ambient temperature is displayed

      Open circuit: -23.3°C (-9.94°F)

      Short circuit: 65.95°C (150.71°F)

      OK
      The display is as specified in the normal condition column.
      Result
      Result Proceed to
      NG A
      OK (Checking from PROBLEM SYMPTOMS TABLE) B
      OK (Checking from DTC) C

  2. Click here

    INSPECT AMBIENT TEMPERATURE SENSOR


    1. A017FDXE16

      Remove the ambient temperature sensor (Click here).

    2. Measure the resistance according to the value(s) in the table below.

      Standard resistance
      Tester Connection Condition Specified Condition
      A7-1 - A7-2 10°C (50°F) 3.00 to 3.73 kΩ
      A7-1 - A7-2 15°C (50°F) 2.45 to 2.88 kΩ
      A7-1 - A7-2 20°C (68°F) 1.95 to 2.30 kΩ
      A7-1 - A7-2 25°C (77°F) 1.60 to 1.80 kΩ
      A7-1 - A7-2 30°C (86°F) 1.28 to 1.47 kΩ
      A7-1 - A7-2 35°C (95°F) 1.00 to 1.22 kΩ
      A7-1 - A7-2 40°C (104°F) 0.80 to 1.00 kΩ
      A7-1 - A7-2 45°C (113°F) 0.65 to 0.85 kΩ
      A7-1 - A7-2 50°C (122°F) 0.50 to 0.70 kΩ
      A7-1 - A7-2 55°C (131°F) 0.44 to 0.60 kΩ
      A7-1 - A7-2 60°C (140°F) 0.36 to 0.50 kΩ
      Note:
      • Touching the sensor even slightly may change the resistance value. Be sure to hold the connector of the sensor.

      • When measuring, the sensor temperature must be the same as the ambient temperature.

      Tip:

      As the temperature increases, the resistance decreases (see the graph).


  3. Click here

    CHECK HARNESS AND CONNECTOR (AMBIENT TEMPERATURE SENSOR - AIR CONDITIONING AMPLIFIER)


    1. A017BTLE03

      Disconnect the A7 sensor connector.

    2. Disconnect the D33 amplifier connector.

    3. Measure the resistance according to the value(s) in the table below.

      Standard resistance
      Tester Connection Condition Specified Condition
      A7-1 - D33-5 (TAM) Always Below 1 Ω
      A7-2 - D33-13 (SG-2) Always Below 1 Ω
      D33-5 (TAM) - Body ground Always 10 kΩ or higher
      D33-13 (SG-2) - Body ground Always 10 kΩ or higher

  4. Click here

    REPLACE AIR CONDITIONING AMPLIFIERClick here

  5. Click here

    REPAIR OR REPLACE HARNESS OR CONNECTOR

  6. Click here

    REPLACE AMBIENT TEMPERATURE SENSORClick here

  7. Click here

    REPLACE AIR CONDITIONING AMPLIFIERClick here

  8. Click here

    PROCEED TO NEXT CIRCUIT INSPECTION SHOWN IN PROBLEM SYMPTOMS TABLEClick here