REFRIGERANT(for HFO-1234yf(R1234yf)) ON-VEHICLE INSPECTION
PROCEDURE
INSPECT REFRIGERANT PRESSURE
This method uses a refrigerant recovery unit set to locate problem areas. Read the refrigerant pressure when the test conditions are established.
Test conditions:
Temperature at the air inlet with the air recirculation switch set at RECIRC is 30 to 35°C (86 to 95°F).
Engine is running at 1500 rpm.
All doors are fully open.
Blower speed control switch is set to HI.
A/C switch is on.
Gauge readings (Reference):
Table 1. Text in Illustration *a
Pressure on low-pressure side
*b
Blower HI Zone
*c
Blower LO Zone
*d
Pressure on high-pressure side
-
Normally functioning refrigeration system.
Gauge Reading
Pressure Side
Refrigerant Volume
Low
0.15 to 0.25 MPa (1.5 to 2.5 kgf/cm2)
High
1.37 to 1.57 MPa (14 to 16 kgf/cm2)
The A/C system periodically changes between normal and improper function due to moisture in the refrigerant system.
Table 2. Text in Illustration *a
Low Pressure Side
*b
High Pressure Side
Symptom
Probable Cause
Diagnosis
Corrective Action
During operation, pressure on low pressure side cycles between normal and vacuum
Moisture in refrigeration system freezes at expansion valve orifice, causing temporary stop of cycle. However, when melted, normal state is restored.
Dryer is overly saturated
Moisture in refrigeration system freezes at expansion valve orifice and blocks refrigerant circulation
Replace cooler dryer
Remove moisture from cycle by repeatedly evacuating air
Supply appropriate volume of new refrigerant
The A/C system does not function effectively due to insufficient refrigerant.
Table 3. Text in Illustration *a
Low Pressure Side
*b
High Pressure Side
Symptom
Probable Cause
Diagnosis
Corrective Action
Pressure low on both low and high pressure sides
Cooling performance insufficient
Gas leakage from refrigeration system
Insufficient refrigerant
Refrigerant leakage
Check for gas leakage and repair if necessary
Supply appropriate volume of new refrigerant
If indicated pressure value close to 0 with gauge connected, create vacuum after inspecting and repairing location of leakage
The A/C system does not function effectively due to poor circulation of the refrigerant.
Table 4. Text in Illustration *a
Low Pressure Side
*b
High Pressure Side
Symptom
Probable Cause
Diagnosis
Corrective Action
Pressure low on both low and high pressure sides
Frost exists on piping from condenser to A/C unit
Refrigerant flow obstructed by dirt in condenser
Condenser clogged
Replace condenser
The A/C system does not function or functions intermittently because the refrigerant does not circulate.
Table 5. Text in Illustration *a
Low Pressure Side
*b
High Pressure Side
Symptom
Probable Cause
Diagnosis
Corrective Action
Vacuum indicated on low pressure side, and extremely low pressure indicated on high pressure side
Frost or condensation seen on piping on both sides of condenser or expansion valve
Refrigerant flow obstructed by moisture or dirt in refrigeration system
Refrigerant flow obstructed by gas leakage from expansion valve
Refrigerant does not circulate
Check expansion valve refrigerant
Clean expansion valve using compressed air
Replace condenser
Evacuate air and charge system with appropriate volume of new refrigerant
For gas leakage from expansion valve, replace expansion valve
The A/C system does not function effectively due to the system being overcharged with refrigerant or insufficient cooling of the condenser.
Table 6. Text in Illustration *a
Low Pressure Side
*b
High Pressure Side
Symptom
Probable Cause
Diagnosis
Corrective Action
Pressure extremely high on both low and high-pressure sides
Excessive refrigerant
Cooling performance of condenser insufficient
Condenser is dirty
Condenser fan motor is malfunctioning
Excessive refrigerant
Clean condenser
Check condenser fan motor operation
If actions taken in 1 and 2 do not solve problem, check amount of refrigerant and adjust amount of refrigerant to appropriate amount
The A/C system does not function due to air in the refrigeration system.
CAUTION:The low-pressure piping may be very hot and cause serious burns.
Note:These gauge indications occur when the refrigeration system opens and the system is charged with refrigerant without vacuum purging.
Table 7. Text in Illustration *a
Low Pressure Side
*b
High Pressure Side
Symptom
Probable Cause
Diagnosis
Corrective Action
Pressure extremely high on both low and high-pressure sides
Low-pressure piping is too hot to touch
Air in refrigeration system
Air in refrigeration system
Vacuum purging insufficient
Check if compressor oil is dirty or insufficient
Evacuate air and charge system with new refrigerant
The A/C system does not function effectively due to an expansion valve malfunction.
Table 8. Text in Illustration *a
Low Pressure Side
*b
High Pressure Side
Symptom
Probable Cause
Diagnosis
Corrective Action
Pressure extremely high on both low and high-pressure sides
Frost or condensation on piping on low-pressure side
Problem with expansion valve
Excessive refrigerant in low pressure piping
Expansion valve open too widely
Replace expansion valve
The A/C system does not function due to a defective compressor.
Table 9. Text in Illustration *a
Low Pressure Side
*b
High Pressure Side
Symptom
Probable Cause
Diagnosis
Corrective Action
Pressure extremely high on both low and high-pressure sides
Pressure extremely low on high pressure side
Internal leakage in compressor
Compression failure
Leakage from damaged valve or broken sliding parts
Repair or replace compressor