AIR CONDITIONING SYSTEM(for Automatic Air Conditioning System), Diagnostic DTC:B1423/23
| DTC Code | DTC Name |
|---|---|
| B1423/23 | Pressure Sensor Circuit |
DESCRIPTION
This DTC is stored if refrigerant pressure on the high pressure side is extremely low (176 kPa (1.8 kgf/cm2, 26 psi) or less) or extremely high (3025 kPa (30.8 kgf/cm2, 439 psi) or more). The air conditioner pressure sensor, which is installed on the high pressure side pipe to detect refrigerant pressure, sends a refrigerant pressure signal to the air conditioning amplifier assembly. The air conditioning amplifier assembly converts this signal to a pressure value according to the sensor characteristics and uses it to control the compressor.
DTC No. |
Detection Item |
DTC Detection Condition |
Trouble Area |
Memory |
|---|---|---|---|---|
B1423/23 |
Pressure Sensor Circuit |
|
|
- |
WIRING DIAGRAM
CAUTION / NOTICE / HINT
If DTC B1423/23 and B14B8 are output at the same time, troubleshoot for DTC B1423/23 first.
PROCEDURE
CHECK HARNESS AND CONNECTOR (POWER SOURCE CIRCUIT)
Disconnect the A16 air conditioner pressure sensor connector.
Measure the voltage according to the value(s) in the table below.
Standard Voltage
Tester Connection
Condition
Specified Condition
A16-3 (+) - Body ground
Ignition switch ON
4.75 to 5.25 V
Result
Proceed to
OK
NG
NG CHECK HARNESS AND CONNECTOR (AIR CONDITIONING AMPLIFIER ASSEMBLY - AIR CONDITIONER PRESSURE SENSOR)Click here
CHECK HARNESS AND CONNECTOR (GROUND CIRCUIT)
Measure the resistance according to the value(s) in the table below.
Standard Resistance
Tester Connection
Condition
Specified Condition
A16-1 (-) - Body ground
Always
Below 1 Ω
Result
Proceed to
OK
NG
NG CHECK HARNESS AND CONNECTOR (AIR CONDITIONING AMPLIFIER ASSEMBLY - AIR CONDITIONER PRESSURE SENSOR)Click here
INSPECT AIR CONDITIONER PRESSURE SENSOR (SENSOR SIGNAL CIRCUIT)
Reconnect the A16 air conditioner pressure sensor connector.
Remove the air conditioning amplifier assembly with the connectors still connected.
-
*a
Component with harness connected
(Air Conditioning Amplifier Assembly)
Measure the voltage according to the value(s) in the table below.
Standard Voltage
Tester Connection
Condition
Specified Condition
E28-9 (PRE) - Body ground
Ignition switch ON
(A/C: Off)
0.74 to 4.62 V
Tip:If the voltage is not as specified, there may be a malfunction in the air conditioning amplifier assembly, air conditioner pressure sensor, or wire harness. It is also possible that the amount of refrigerant may not be appropriate.
Result
Proceed to
OK
NG
NG CHECK HARNESS AND CONNECTOR (AIR CONDITIONING AMPLIFIER ASSEMBLY - AIR CONDITIONER PRESSURE SENSOR)Click here
INSPECT AIR CONDITIONER PRESSURE SENSOR (SENSOR SIGNAL CIRCUIT)
Measure the voltage when the following conditions are met.
Item
Condition
Vehicle doors
Fully open
Temperature setting
MAX COLD
Blower speed
HI
A/C switch
On
Recirculation/fresh switch
RECIRCULATION
Interior temperature
25 to 35°C (77 to 95°F)
Engine speed
2000 rpm
Note:If refrigerant pressure on the high pressure side becomes extremely high during the inspection (if the voltage exceeds 4.8 V), the fail-safe function stops compressor operation. Therefore, measure the voltage before the fail-safe operation.
It is necessary to measure the voltage for a certain amount of time (approximately 10 minutes) because the malfunction may recur after a while.
Tip:When the outside air temperature is low (below -1.5°C (29.3°F)), the compressor stops due to operation of the thermistor assembly and the No. 1 cooler thermistor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
-
*a
Component with harness connected
(Air Conditioning Amplifier Assembly)
Measure the voltage according to the value(s) in the table below.
Standard Voltage
Tester Connection
Condition
Specified Condition
E28-9 (PRE) - Body ground
Ignition switch ON
(A/C: On)
0.74 to 4.62 V
Result
Result
Proceed to
OK (When troubleshooting according to DTC)
A
OK (When troubleshooting according to Problem Symptoms Table)
B
NG
C
INSPECT COOLING FAN SYSTEM
Check if the cooling fan operates normally.
for 1ND-TV:Click here
for 1NR-FE:Click here
for 1ZR-FAE:Click here
for 1ZR-FE:Click here
for 2ZR-FE:Click here
for 8NR-FTS:Click here
Result
Proceed to
OK
NG
NG GO TO COOLING FAN SYSTEM
for 1ND-TV:Click here
for 1NR-FE:Click here
for 1ZR-FAE:Click here
for 1ZR-FE:Click here
for 2ZR-FE:Click here
for 8NR-FTS:Click here
CHARGE SYSTEM WITH REFRIGERANT
Use a refrigerant recovery unit to recover refrigerant.
Evacuate the A/C system.
Add an appropriate amount of refrigerant.
for HFC-134a (R134a):Click here
for HFO-1234yf (R1234yf):Click here
Tip:If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the cooler expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for the DTC.
Result
Proceed to
NEXT
RECHECK FOR DTC
Recheck for DTCs when the following conditions are met.
Item
Condition
Vehicle doors
Fully open
Temperature setting
MAX COLD
Blower speed
HI
A/C switch
On
Recirculation/fresh switch
RECIRCULATION
Interior temperature
25 to 35°C (77 to 95°F)
Engine speed
2000 rpm
Body Electrical > Air Conditioner > Trouble Codes
Note:If refrigerant pressure on the high pressure side becomes high, the DTC will be stored. It is necessary to operate the A/C system for a certain amount of time (approximately 10 minutes) because the DTC may be stored after the air conditioning operates for a while.
Tip:When the outside air temperature is low (below -1.5°C (29.3°F)), the compressor stops due to operation of the thermistor assembly and the No. 1 cooler thermistor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the cooler expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for the DTC. If the DTC is not output after this work, it indicates that the cooler dryer in the cooler condenser assembly is not able to absorb moisture in the refrigerant cycle. It is necessary to replace the cooler dryer in order to complete the repair.
Result
Result
Proceed to
DTC B1423/23 is output
A
DTC B1423/23 is not output
B
REPLACE COOLER EXPANSION VALVE
Replace the cooler expansion valve with a new one.
Tip:Replace the cooler expansion valve with a new one because the cooler expansion valve is either stuck or clogged.
Result
Proceed to
NEXT
CHARGE SYSTEM WITH REFRIGERANT
Use a refrigerant recovery unit to recover refrigerant.
Evacuate the A/C system.
Add an appropriate amount of refrigerant.
for HFC-134a (R134a):Click here
for HFO-1234yf (R1234yf):Click here
Tip:If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the cooler expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for the DTC.
Result
Proceed to
NEXT
RECHECK FOR DTC
Recheck for DTCs when the following conditions are met.
Item
Condition
Vehicle doors
Fully open
Temperature setting
MAX COLD
Blower speed
HI
A/C switch
On
Recirculation/fresh switch
RECIRCULATION
Interior temperature
25 to 35°C (77 to 95°F)
Engine speed
2000 rpm
Body Electrical > Air Conditioner > Trouble Codes
Note:If refrigerant pressure on the high pressure side becomes high, the DTC will be stored. It is necessary to operate the A/C system for a certain amount of time (approximately 10 minutes) because the DTC may be stored after the air conditioning operates for a while.
Tip:When the outside air temperature is low (below -1.5°C (29.3°F)), the compressor stops due to operation of the thermistor assembly and the No. 1 cooler thermistor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
If refrigerant pressure is not normal after replacing the cooler expansion valve with a new or known good one, the cooler condenser assembly or pipes may be clogged due to dirt, dust or other foreign matter. In this case, clean or replace the cooler condenser assembly or pipes.
Result
Result
Proceed to
DTC B1423/23 is not output
A
DTC B1423/23 is output
B
A END
B CLEAN OR REPLACE CONDENSER ASSEMBLY WITH RECEIVER
CHECK HARNESS AND CONNECTOR (AIR CONDITIONING AMPLIFIER ASSEMBLY - AIR CONDITIONER PRESSURE SENSOR)
Disconnect the A16 air conditioner pressure sensor connector.
Disconnect the E28 air conditioning amplifier assembly connector.
Measure the resistance according to the value(s) in the table below.
Standard Resistance
Tester Connection
Condition
Specified Condition
A16-2 (PR) - E28-9 (PRE)
Always
Below 1 Ω
A16-2 (PR) or E28-9 (PRE) - Body ground
Always
10 kΩ or higher
Result
Proceed to
OK
NG
NG REPAIR OR REPLACE HARNESS OR CONNECTOR
INSPECT FOR A/C SYSTEM LEAK
Install a manifold gauge set.
Recover the refrigerant from the A/C system using a refrigerant recovery unit.
Evacuate the A/C system and check that vacuum can be maintained.
OK
Vacuum can be maintained in the A/C system.
Tip:If vacuum cannot be maintained in the A/C system, refrigerant may be leaking from it. In this case, it is necessary to repair or replace the leaking part of the A/C system.
Result
Proceed to
OK
NG
NG REPAIR A/C SYSTEM LEAKClick here
CHARGE SYSTEM WITH REFRIGERANT
Use a refrigerant recovery unit to recover refrigerant.
Evacuate the A/C system.
Add an appropriate amount of refrigerant.
for HFC-134a (R134a):Click here
for HFO-1234yf (R1234yf):Click here
Tip:If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the cooler expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for the DTC.
Result
Proceed to
NEXT
RECHECK FOR DTC
Recheck for DTCs when the following conditions are met.
Item
Condition
Vehicle doors
Fully open
Temperature setting
MAX COLD
Blower speed
HI
A/C switch
On
Recirculation/fresh switch
RECIRCULATION
Interior temperature
25 to 35°C (77 to 95°F)
Engine speed
2000 rpm
Body Electrical > Air Conditioner > Trouble Codes
Note:If refrigerant pressure on the high pressure side becomes high, the DTC will be stored. It is necessary to operate the A/C system for a certain amount of time (approximately 10 minutes) because the DTC may be stored after the air conditioning operates for a while.
Tip:When the outside air temperature is low (below -1.5°C (29.3°F)), the compressor stops due to operation of the thermistor assembly and the No. 1 cooler thermistor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
Result
Result
Proceed to
DTC B1423/23 is output
A
DTC B1423/23 is not output
B
Note:If the DTC was stored due to an insufficient or excessive amount of refrigerant, the problem may have been solved after performing the previous step. However, the root cause of insufficient refrigerant may be refrigerant leaks. The root cause of excessive refrigerant may be adding too much refrigerant when the level was insufficient. Therefore, identify and repair the area where refrigerant leaks from as necessary.
B END
INSPECT AIR CONDITIONER PRESSURE SENSOR
Install a manifold gauge set.
Reconnect the A16 air conditioner pressure sensor connector.
Turn the ignition switch to ON.
-
*a
Component with harness connected
(Air Conditioning Amplifier Assembly)
Measure the voltage according to the value(s) in the table below.
Standard Voltage
Tester Connection
Condition
Specified Condition
E28-9 (PRE) - E28-13 (SG-2)
Refrigerant pressure: (less than 3025 kPa (30.9 kgf/cm2, 439 psi) and more than 176 kPa (1.8 kgf/cm2, 25 psi))
0.74 to 4.62 V
Result
Proceed to
OK
NG
REPAIR A/C SYSTEM LEAK
Identify the area where refrigerant leaks from.
for HFC-134a (R134a):Click here
for HFO-1234yf (R1234yf):Click here
Repair the identified area of the A/C system.
Evacuate the A/C system.
Result
Proceed to
NEXT
NEXT CHARGE SYSTEM WITH REFRIGERANT
for HFC-134a (R134a):Click here
for HFO-1234yf (R1234yf):Click here
CHECK HARNESS AND CONNECTOR (AIR CONDITIONING AMPLIFIER ASSEMBLY - AIR CONDITIONER PRESSURE SENSOR)
Disconnect the E28 air conditioning amplifier assembly connector.
Measure the resistance according to the value(s) in the table below.
Standard Resistance
Tester Connection
Condition
Specified Condition
A16-1 (-) - E28-13 (SG-2)
Always
Below 1 Ω
A16-1 (-) or E28-13 (SG-2) - Body ground
Always
10 kΩ or higher
Result
Proceed to
OK
NG
NG REPAIR OR REPLACE HARNESS OR CONNECTOR
CHECK HARNESS AND CONNECTOR (AIR CONDITIONING AMPLIFIER ASSEMBLY - AIR CONDITIONER PRESSURE SENSOR)
Disconnect the E28 air conditioning amplifier assembly connector.
Measure the resistance according to the value(s) in the table below.
Standard Resistance
Tester Connection
Condition
Specified Condition
A16-3 (+) - E28-10 (S5-3)
Always
Below 1 Ω
A16-3 (+) or E28-10 (S5-3) - Body ground
Always
10 kΩ or higher
Result
Proceed to
OK
NG
NG REPAIR OR REPLACE HARNESS OR CONNECTOR