AIR CONDITIONING SYSTEM(for Manual Air Conditioning System), Diagnostic DTC:B1423
| DTC Code | DTC Name |
|---|---|
| B1423 | Pressure Sensor Circuit |
DESCRIPTION
This DTC is stored when refrigerant pressure is extremely low (0.176 MPa [1.8 kgf/cm2, 25.5 psi] or less) or extremely high (3.025 MPa [30.9 kgf/cm2, 438.6 psi] or more). The air conditioning pressure sensor, which is installed on the pipe of the high pressure side to detect refrigerant pressure, outputs the refrigerant pressure signal to the air conditioning amplifier assembly. The air conditioning amplifier assembly converts the signal to a pressure value according to the sensor characteristics to control the compressor.
Be sure to check the refrigerant volume first when this DTC is output because this DTC can also be stored if there is no refrigerant in the cycle.
DTC Code |
DTC Detection Condition |
Trouble Area |
|---|---|---|
B1423 |
Either condition is met:
|
|
WIRING DIAGRAM
PROCEDURE
CHECK HARNESS AND CONNECTOR (PRESSURE SENSOR - BATTERY AND BODY GROUND)
-
Disconnect the A16 sensor connector.
Measure the voltage according to the value(s) in the table below.
Standard Voltage
Tester Connection
Switch Condition
Specified Condition
A16-3 (+) - Body ground
Ignition switch ON
4.75 to 5.25 V
Measure the resistance according to the value(s) in the table below.
Standard Resistance
Tester Connection
Condition
Specified Condition
A16-1 (-) - Body ground
Always
Below 1 Ω
Table 1. Text in Illustration *1
Front view of wire harness connector
(to Air Conditioning Pressure Sensor)
CHECK HARNESS AND CONNECTOR (PRESSURE SENSOR - AIR CONDITIONING AMPLIFIER)Click here
-
CHECK AIR CONDITIONING PRESSURE SENSOR (SENSOR SIGNAL CIRCUIT)
-
Reconnect the A16 sensor connector.
Remove the air conditioning amplifier assembly with its connectors still connected (Click here).
Measure the voltage according to the value(s) in the table below.
Standard Voltage
Tester Connection
Switch Condition
Specified Condition
H118-7 (PRE) - Body ground
Ignition switch ON
A/C switch off
0.70 to 4.61 V
Table 2. Text in Illustration *1
Component with harness connected
(Air Conditioning Amplifier Assembly)
Tip:If the measured voltage is not within the normal range, there may be a malfunction in the air conditioning amplifier assembly, air conditioning pressure sensor or wire harness. It is also possible that the amount of refrigerant may not be appropriate.
CHECK HARNESS AND CONNECTOR (PRESSURE SENSOR - AIR CONDITIONING AMPLIFIER)Click here
-
CHECK AIR CONDITIONING PRESSURE SENSOR (SENSOR SIGNAL CIRCUIT)
Measure the voltage when the following conditions are met.
Table 3. Measurement Condition Item
Condition
Engine Speed
2000 rpm
Vehicle Doors
Fully open
Temperature Setting
MAX COOL
Blower Speed
Hi
A/C Switch
On
R/F Switch
Recirculation
Interior Temperature
25 to 35°C (77 to 95°F)
Note:If refrigerant pressure on the high pressure side becomes extremely high during the inspection (if the voltage exceeds 4.8 V), the fail-safe function stops compressor operation. Therefore, measure the voltage before the fail-safe operation.
It is necessary to measure the voltage for a certain amount of time (approximately 10 minutes) because the problem symptom may recur after a while.
Tip:When the outside air temperature is low (below -1.5°C [29.3°F]), the compressor stops due to operation of the ambient temperature sensor and evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
-
Measure the voltage according to the value(s) in the table below.
Standard Voltage
Tester Connection
Switch Condition
Specified Condition
H118-7 (PRE) - Body ground
Ignition switch ON
A/C switch on
0.70 to 4.61 V
Table 4. Text in Illustration *1
Component with harness connected
(Air Conditioning Amplifier Assembly)
Table 5. Result Result
Proceed to
OK (When troubleshooting according to Problem Symptoms Table)
A
OK (When troubleshooting according to the DTC)
B
NG
C
CHARGE REFRIGERANTClick here
CHECK HARNESS AND CONNECTOR (PRESSURE SENSOR - AIR CONDITIONING AMPLIFIER)
-
Disconnect the H118 amplifier connector.
Disconnect the A16 sensor connector.
Measure the resistance according to the value(s) in the table below.
Standard Resistance
Tester Connection
Condition
Specified Condition
A16-1 (-) - H118-5 (SG-2)
Always
Below 1 Ω
A16-3 (+) - H118-24 (S5-3)
Always
Below 1 Ω
H118-5 (SG-2) - Body ground
Always
10 kΩ or higher
H118-24 (S5-3) - Body ground
Always
10 kΩ or higher
Table 6. Text in Illustration *1
Front view of wire harness connector
(to Air Conditioning Pressure Sensor)
*2
Rear view of wire harness connector
(to Air Conditioning Amplifier Assembly)
REPAIR OR REPLACE HARNESS OR CONNECTOR
-
CHECK HARNESS AND CONNECTOR (PRESSURE SENSOR - AIR CONDITIONING AMPLIFIER)
-
Disconnect the H118 amplifier connector.
Disconnect the A16 sensor connector.
Measure the resistance according to the value(s) in the table below.
Standard Resistance
Tester Connection
Condition
Specified Condition
A16-2 (PR) - H118-7 (PRE)
Always
Below 1 Ω
H118-7 (PRE) - Body ground
Always
10 kΩ or higher
Table 7. Text in Illustration *1
Front view of wire harness connector
(to Air Conditioning Pressure Sensor)
*2
Rear view of wire harness connector
(to Air Conditioning Amplifier Assembly)
REPAIR OR REPLACE HARNESS OR CONNECTOR
-
CHECK FOR AIR CONDITIONING SYSTEM LEAK
Install a manifold gauge set.
Recover the refrigerant from the air conditioning system using a refrigerant recovery unit.
Evacuate the air conditioning system and check that vacuum can be maintained in it.
OK
Vacuum can be maintained in the air conditioning system.
Tip:If vacuum cannot be maintained in the air conditioning system, refrigerant may be leaking from it. In this case, it is necessary to repair or replace the leaking part of the air conditioning system.
REPAIR AIR CONDITIONING SYSTEM LEAKClick here
CHARGE REFRIGERANT
Add an appropriate amount of refrigerant.
for HFC-134a(R134a):Click here
for HFO-1234yf(R1234yf):Click here
CHECK FOR DTC
Check for DTCs when the following conditions are met (Click here).
Table 8. Measurement Condition Item
Condition
Engine Speed
2000 rpm
Vehicle Doors
Fully open
Temperature Setting
MAX COOL
Blower Speed
Hi
A/C Switch
On
R/F Switch
Recirculation
Interior Temperature
25 to 35°C (77 to 95°F)
Note:If refrigerant pressure on the high pressure side becomes high, a DTC will be stored. Therefore, it is necessary to check for DTCs after a certain amount of time (approximately 10 minutes) has passed because the DTC may be stored after the air conditioning system operates for a while.
Tip:When the outside air temperature is low (below -1.5°C [29.3°F]), the compressor stops due to operation of the ambient temperature sensor and evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
OK
DTC B1423 is not output.
Note:If the DTC was stored due to an insufficient or excessive amount of refrigerant, the problem may have been solved after performing the previous step. However, the root cause of insufficient refrigerant may be refrigerant leakage. Therefore, identify and repair the area where refrigerant leakage as necessary. The root cause of excessive refrigerant may be adding too much refrigerant.
END (COOLER EXPANSION VALVE IS FAULTY)
CHECK AIR CONDITIONING PRESSURE SENSOR
Install a manifold gauge set.
Table 9. Text in Illustration *1
Component with harness connected
(Air Conditioning Amplifier Assembly)
-
-
Reconnect the A16 sensor connector.
Remove the air conditioning amplifier assembly with its connectors still connected (Click here).
Turn the ignition switch to ON.
Measure the voltage according to the value(s) in the table below.
Standard Voltage
Tester Connection
Switch Condition
Specified Condition
H118-7 (PRE) - H118-5 (SG-2)
Ignition switch ON
Refrigerant pressure normal (less than 3.025 MPa [30.9 kgf/cm2, 438.6 psi] and more than 0.176 MPa [1.8 kgf/cm2, 25.5 psi])
0.70 to 4.61 V
Ignition switch ON
Refrigerant pressure abnormal (less than 0.176 MPa [1.8 kgf/cm2, 25.5 psi])
Below 0.70 V
Ignition switch ON
Refrigerant pressure abnormal (more than 3.025 MPa [30.9 kgf/cm2, 438.6 psi])
4.61 V or higher
REPAIR AIR CONDITIONING SYSTEM LEAK
Identify the area where refrigerant leaks.
for HFC-134a(R134a):Click here
for HFO-1234yf(R1234yf):Click here
Repair the identified area of the air conditioning system.
Evacuate the air conditioning system.
CHARGE REFRIGERANT
Use a refrigerant recovery unit to recover refrigerant.
Evacuate the air conditioning system.
Add an appropriate amount of refrigerant.
for HFC-134a(R134a):Click here
for HFO-1234yf(R1234yf):Click here
Tip:If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and then check for the DTC.
CHECK FOR DTC
Check for DTCs when the following conditions are met (Click here).
Table 10. Measurement Condition Item
Condition
Engine Speed
2000 rpm
Vehicle Doors
Fully open
Temperature Setting
MAX COOL
Blower Speed
Hi
A/C Switch
On
R/F Switch
Recirculation
Interior Temperature
25 to 35°C (77 to 95°F)
Note:If refrigerant pressure on the high pressure side becomes high, a DTC will be stored. Therefore, it is necessary to check for DTCs after a certain amount of time (approximately 10 minutes) has passed because the DTC may be stored after the air conditioning system operates for a while.
Tip:When the outside air temperature is low (below -1.5°C [29.3°F]), the compressor stops due to operation of the ambient temperature sensor and evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for the DTC. If the DTC is not output after this procedure, it indicates that the cooler dryer in the condenser assembly with receiver is not able to absorb moisture in the refrigerant cycle. In this case, to complete the repair, it is necessary to replace the cooler dryer.
Table 11. Result Result
Proceed to
DTC B1423 is output
A
DTC B1423 is not output (for 1WW)
B
DTC B1423 is not output (except 1WW)
C
REPLACE COOLER EXPANSION VALVE
Replace the cooler expansion valve with a new or normally functioning one (Click here).
Tip:Replace the cooler expansion valve with a new or normally functioning one because the cooler expansion valve is either stuck or clogged.
CHARGE REFRIGERANT
Add an appropriate amount of refrigerant.
for HFC-134a(R134a):Click here
for HFO-1234yf(R1234yf):Click here
CHECK FOR DTC
Check for DTCs when the following conditions are met (Click here).
Table 12. Measurement Condition Item
Condition
Engine Speed
2000 rpm
Vehicle Doors
Fully open
Temperature Setting
MAX COOL
Blower Speed
Hi
A/C Switch
On
R/F Switch
Recirculation
Interior Temperature
25 to 35°C (77 to 95°F)
Note:If refrigerant pressure on the high pressure side becomes high, a DTC will be stored. Therefore, it is necessary to check for DTCs after a certain amount of time (approximately 10 minutes) has passed because the DTC may be stored after the air conditioning system operates for a while.
Tip:When the outside air temperature is low (below -1.5°C [29.3°F]), the compressor stops due to operation of the ambient temperature sensor and evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
If refrigerant pressure is not normal after replacing the expansion valve with a new or normally functioning one, the condenser assembly with receiver or pipes may be clogged due to dirt, dust or other contaminants. In this case, clean or replace the condenser assembly with receiver or pipes.
Table 13. Result Result
Proceed to
DTC B1423 is not output
A
DTC B1423 is output (for 1WW)
B
DTC B1423 is output (except 1WW)
C
END (COOLER EXPANSION VALVE IS FAULTY)