AIR CONDITIONING SYSTEM(for Automatic Air Conditioning System), Diagnostic DTC:B1411/11
| DTC Code | DTC Name |
|---|---|
| B1411/11 | Room Temperature Sensor Circuit |
DESCRIPTION
The cooler thermistor (room temperature sensor) for the front seat is installed in the instrument panel to detect the room temperature and control the heater and air conditioner auto mode. The resistance of the room temperature sensor changes in accordance with the front room temperature. As the temperature decreases, the resistance increases. As the temperature increases, the resistance decreases.
The air conditioning amplifier assembly applies voltage (5 V) to the room temperature sensor and reads voltage changes as the resistance of the room temperature sensor changes. This sensor also sends the appropriate signals to the air conditioning amplifier assembly.
DTC Code |
DTC Detection Condition |
Trouble Area |
|---|---|---|
B1411/11 |
An open or short in the room temperature sensor circuit. |
|
WIRING DIAGRAM
PROCEDURE
READ VALUE USING INTELLIGENT TESTER
Use the Data List to check if the cooler thermistor (room temperature sensor) is functioning properly.
Table 1. Air Conditioner Tester Display
Measurement Item/Range
Normal Condition
Diagnostic Note
Room Temperature Sensor
Room temperature sensor /
Min.: -6.5°C (20.3°F)
Max.: 57.25°C (135.05°F)
Actual room temperature for front seat displayed
Open in the circuit: -6.5°C (20.3°F).
Short in the circuit: 57.25°C (135.05°F).
OK
The display is as specified in the normal condition column.
Table 2. Result Result
Proceed to
OK (When troubleshooting according to Problem Symptoms Table)
A
OK (When troubleshooting according to the DTC)
B
NG
C
INSPECT COOLER THERMISTOR (ROOM TEMPERATURE SENSOR)
Remove the room temperature sensor (Click here).
Measure the resistance according to the value(s) in the table below.
Standard Resistance
Tester Connection
Condition
Specified Condition
1 - 2
10°C (50°F)
3.00 to 3.73 kΩ
15°C (59°F)
2.45 to 2.88 kΩ
20°C (68°F)
1.95 to 2.30 kΩ
25°C (77°F)
1.60 to 1.80 kΩ
30°C (86°F)
1.28 to 1.47 kΩ
35°C (95°F)
1.00 to 1.22 kΩ
40°C (104°F)
0.80 to 1.00 kΩ
45°C (113°F)
0.65 to 0.85 kΩ
50°C (122°F)
0.50 to 0.70 kΩ
55°C (131°F)
0.44 to 0.60 kΩ
60°C (140°F)
0.36 to 0.50 kΩ
Note:Even slightly touching the sensor may change the resistance value. Be sure to hold the connector of the sensor.
When measuring, the sensor temperature must be the same as the ambient temperature.
Tip:As the temperature increases, the resistance decreases (refer to the graph).
CHECK HARNESS AND CONNECTOR (ROOM TEMPERATURE SENSOR - AIR CONDITIONING AMPLIFIER)
Disconnect the H38 sensor connector.
Disconnect the H46 amplifier connector.
Measure the resistance according to the value(s) in the table below.
Standard Resistance
Tester Connection
Condition
Specified Condition
H38-1 - H46-29 (TR)
Always
Below 1 Ω
H38-2 - H46-34 (SG-1)
H46-29 (TR) - Body ground
Always
10 kΩ or higher
H46-34 (SG-1) - Body ground
Table 3. Text in Illustration *1
Front view of wire harness connector
(to Room Temperature Sensor)
*2
Rear view of wire harness connector
(to Air Conditioning Amplifier Assembly)
REPAIR OR REPLACE HARNESS OR CONNECTOR