OUTLINE
The automatic air conditioning system uses left and right independent temperature control and neural network control to enhance comfort.
S-FLOW control is used to concentrate the air outlets on the front seats when the S-FLOW switch is turned on.
SPECIFICATIONS
Ventilation and Heater Core
| Component | Specifications | |
|---|---|---|
| Heater Radiator Unit Sub-assembly | Type | Straight Flow Aluminum-II (SFA-II) |
| Size (W x H x L) | 222.3 mm x 120 mm x 27 mm (8.8 in. x 4.7 in. x 1.1 in.) | |
| Fin Pitch | 1.8 mm (0.07 in.) | |
| Blower Motor with Fan Sub-assembly | Motor Type | DC Ferrite Brushless |
| Fan Type | Sirocco | |
| Fan Size (Dia. x H) | 128.2 mm x 70 mm (5.0 in. x 2.8 in.) | |
Air Conditioning
| Component | Specifications | |
|---|---|---|
| Cooler Condenser Assembly | Type | Multi-Flow IV (MF-IV) Sub-cool |
| Size (W x H x L) | 666 mm x 287 mm x 22 mm (26.2 in. x 11.3 in. x 0.9 in.) | |
| Fin Pitch | 2.7 mm (0.1 in.) | |
| Compressor with Motor Assembly | ES27C | |
| Refrigerant | Type | HFC-134a*1, HFO-1234yf*2 |
| No. 1 Cooler Evaporator Sub-assembly | Type | Beneficial Refrigerant Stream (BRS) |
| Size (W x H x L) | 239.5 mm x 231 mm x 38 mm (9.4 in. x 9.1 in. x 1.5 in.) | |
| Fin Pitch | 3.0 mm (0.1 in.) | |
*1: Models using HFC-134a refrigerant
*2: Models using HFO-1234yf refrigerant
MAIN FEATURES
The air conditioning system has the following features:
| Feature | Outline |
|---|---|
| High Performance |
|
| Light Weight |
|
| Compact | A blower motor with a built-in blower motor controller is used to achieve a compact construction. |
| Others | The following parts are used to ensure high cooling performance while achieving a compact and lightweight construction:
|
PRECAUTION
Precaution for Refrigerant HFO-1234yf
Always use HFO-1234yf as the refrigerant.
CAUTION:
Do not charge the system with refrigerant near open flames, as HFO-1234yf is combustible.
When charging the system with refrigerant, make sure the area is well ventilated (especially be careful in areas where the gas can easily accumulate such as under lifts and in garage pits, as the gas is heavier than air).
Follow any local regulations regarding combustible gases.
Be sure to use a refrigerant recovery unit that is compatible with HFO-1234yf systems.
Tech Tips
The shape of the service port for refrigerant charging has an exclusive design conforming to international standards for HFO-1234yf to prevent improper refrigerant charging.
Compressor Oil
Always use ND-OIL 11 as the compressor oil.
When parts of the air conditioning system are removed, quickly block off any areas that are exposed to the outside air with plugs, vinyl tape, etc., as the oil used for HFO-1234yf systems absorbs moisture easily.
Do not allow the compressor oil to spray, as the oil used for HFO-1234yf systems has harmful effects on acrylic resins.