ROOM TEMPERATURE SENSOR (for Automatic Air Conditioning System) INSPECTION

Click here
Click here Click here
  1. Click here

    INSPECT COOLER THERMISTOR (ROOM TEMPERATURE SENSOR)


    1. Measure the resistance according to the value(s) in the table below.

      Standard Resistance
      Tester Connection Condition Specified Condition
      1 - 2 10°C (50°F) 3.00 to 3.73 kΩ
      1 - 2 15°C (59°F) 2.45 to 2.88 kΩ
      1 - 2 20°C (68°F) 1.95 to 2.30 kΩ
      1 - 2 25°C (77°F) 1.60 to 1.80 kΩ
      1 - 2 30°C (86°F) 1.28 to 1.47 kΩ
      1 - 2 35°C (95°F) 1.00 to 1.22 kΩ
      1 - 2 40°C (104°F) 0.80 to 1.00 kΩ
      1 - 2 45°C (113°F) 0.65 to 0.85 kΩ
      1 - 2 50°C (122°F) 0.50 to 0.70 kΩ
      1 - 2 55°C (131°F) 0.44 to 0.60 kΩ
      1 - 2 60°C (140°F) 0.36 to 0.50 kΩ
      Tip:

      As the temperature increases, the resistance decreases (refer to the graph).

      Note:
      • Touching the sensor even slightly may change the resistance value. Hold the connector of the sensor.


      • When measuring the resistance, the sensor temperature must be the same as the ambient temperature.

      If the result is not as specified, replace the cooler thermistor (room temperature sensor).