VALVE BODY ASSEMBLY INSPECTION


  1. INSPECT SHIFT SOLENOID VALVE SL


    1. A019K1WE02
      Text in Illustration
      *1 Shift Solenoid Valve SL

      Measure the resistance according to the value(s) in the table below.

      Standard Resistance
      Tester Connection Condition Specified Condition
      Solenoid Connector (SL) - Solenoid Body (SL) 20°C (68°F) 11 to 15 Ω

      If the value is not as specified, replace the shift solenoid valve.

    2. Connect a positive (+) lead from the battery to the terminal of the solenoid connector, and a negative (-) lead to the solenoid body, and check the operation of the valve.

      Note

      When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

      OK
      The valve moves and makes an operating sound.

      If the operation cannot be done as specified, replace the shift solenoid valve.

  2. INSPECT SHIFT SOLENOID VALVE SLT


    1. A019MNDE25
      Text in Illustration
      *1

      Component without harness connected

      (Shift Solenoid Valve SLT)

      Measure the resistance according to the value(s) in the table below.

      Standard Resistance
      Tester Connection Condition Specified Condition
      1 - 2 20°C (68°F) 5.0 to 5.6 Ω

      If the value is not as specified, replace the shift solenoid valve.

    2. Connect a positive (+) lead from the battery with a 21 W bulb to terminal 2 and a negative (-) lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

      Note

      When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

      OK
      The valve moves and makes an operating sound.

      If the operation cannot be done as specified, replace the shift solenoid valve.

  3. INSPECT SHIFT SOLENOID VALVE SLU


    1. A019MNDE25
      Text in Illustration
      *1

      Component without harness connected

      (Shift Solenoid Valve SLU)

      Measure the resistance according to the value(s) in the table below.

      Standard Resistance
      Tester Connection Condition Specified Condition
      1 - 2 20°C (68°F) 5.0 to 5.6 Ω

      If the value is not as specified, replace the shift solenoid valve.

    2. Connect a positive (+) lead from the battery with a 21 W bulb to terminal 2 and a negative (-) lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

      Note

      When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

      OK
      The valve moves and makes an operating sound.

      If the operation cannot be done as specified, replace the shift solenoid valve.

  4. INSPECT SHIFT SOLENOID VALVE SL1


    1. A019MNDE25
      Text in Illustration
      *1

      Component without harness connected

      (Shift Solenoid Valve SL1)

      Measure the resistance according to the value(s) in the table below.

      Standard Resistance
      Tester Connection Condition Specified Condition
      1 - 2 20°C (68°F) 5.0 to 5.6 Ω

      If the value is not as specified, replace the shift solenoid valve.

    2. Connect a positive (+) lead from the battery with a 21 W bulb to terminal 2 and a negative (-) lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

      Note

      When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

      OK
      The valve moves and makes an operating sound.

      If the operation cannot be done as specified, replace the shift solenoid valve.

  5. INSPECT SHIFT SOLENOID VALVE SL2


    1. A019MNDE25
      Text in Illustration
      *1

      Component without harness connected

      (Shift Solenoid Valve SL2)

      Measure the resistance according to the value(s) in the table below.

      Standard Resistance
      Tester Connection Condition Specified Condition
      1 - 2 20°C (68°F) 5.0 to 5.6 Ω

      If the value is not as specified, replace the shift solenoid valve.

    2. Connect a positive (+) lead from the battery with a 21 W bulb to terminal 2 and a negative (-) lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

      Note

      When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

      OK
      The valve moves and makes an operating sound.

      If the operation cannot be done as specified, replace the shift solenoid valve.

  6. INSPECT SHIFT SOLENOID VALVE SL3


    1. A019MNDE25
      Text in Illustration
      *1

      Component without harness connected

      (Shift Solenoid Valve SL3)

      Measure the resistance according to the value(s) in the table below.

      Standard Resistance
      Tester Connection Condition Specified Condition
      1 - 2 20°C (68°F) 5.0 to 5.6 Ω

      If the value is not as specified, replace the shift solenoid valve.

    2. Connect a positive (+) lead from the battery with a 21 W bulb to terminal 2 and a negative (-) lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

      Note

      When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

      OK
      The valve moves and makes an operating sound.

      If the operation cannot be done as specified, replace the shift solenoid valve.

  7. INSPECT SHIFT SOLENOID VALVE SL4


    1. A019MNDE25
      Text in Illustration
      *1

      Component without harness connected

      (Shift Solenoid Valve SL4)

      Measure the resistance according to the value(s) in the table below.

      Standard Resistance
      Tester Connection Condition Specified Condition
      1 - 2 20°C (68°F) 5.0 to 5.6 Ω

      If the value is not as specified, replace the shift solenoid valve.

    2. Connect a positive (+) lead from the battery with a 21 W bulb to terminal 2 and a negative (-) lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

      Note

      When using battery voltage during the inspection, do not bring the positive (+) and negative (-) tester probes too close to each other as a short circuit may occur.

      OK
      The valve moves and makes an operating sound.

      If the operation cannot be done as specified, replace the shift solenoid valve.