ROOM TEMPERATURE SENSOR INSPECTION

PROCEDURE


  1. INSPECT COOLER (ROOM TEMP. SENSOR) THERMISTOR


    1. Disconnect the connector from the cooler (room temp. sensor) thermistor.

      A004IDJE01
    2. Measure the resistance according to the value(s) in the table below.

      Standard Resistance
      Tester Connection Condition Specified Condition
      1 - 2 10°C (50°F) 3.00 to 3.73 kΩ
      15°C (59°F) 2.45 to 2.88 kΩ
      20°C (68°F) 1.95 to 2.30 kΩ
      25°C (77°F) 1.60 to 1.80 kΩ
      30°C (86°F) 1.28 to 1.47 kΩ
      35°C (95°F) 1.00 to 1.22 kΩ
      40°C (104°F) 0.80 to 1.00 kΩ
      45°C (113°F) 0.65 to 0.85 kΩ
      50°C (122°F) 0.50 to 0.70 kΩ
      55°C (131°F) 0.44 to 0.60 kΩ
      60°C (140°F) 0.36 to 0.50 kΩ

      Note


      • Hold the sensor only by its connector. Touching the sensor may change the resistance value.

      • When measuring, the sensor temperature must be the same as the ambient temperature.

      Tech Tips

      As the temperature increases, the resistance decreases (see the graph).

      If the resistance is not as specified, replace the cooler (room temp. sensor) thermistor.

      Text in Illustration
      *a

      Component without harness connected

      (cooler (room temp. sensor) thermistor)

      *b Sensing Portion
      *c Resistance (kΩ)
      *d Allowable Range
      *e Temperature (°C (°F))