| DTC Code | DTC Name |
|---|---|
| B1436/45 | Open in Passenger Side Air Mix Damper Position Sensor Circuit |
| B1437/-45 | Short in Passenger Side Air Mix Damper Position Sensor Circuit |
| B1441/E45 | Passenger Side Air Mix Damper Control Servomotor Circuit |
DESCRIPTION
This sensor detects the position of the air mix damper and sends appropriate signals to the A/C amplifier assembly. The position sensor is built into the air mix control servo motor. This adjusts the amount of air passing through the heater core after passing the No. 1 cooler evaporator sub-assembly and controls the temperature of the output air.
Tech Tips
Confirm that no mechanical problem is present because this diagnostic code can be output when either a damper link or the damper is mechanically locked.
| *a | Voltage (V) |
| *b | Damper opening angle |
| DTC No. | DTC Detection Condition | Trouble Area |
|---|---|---|
| B1436/45 | Open in passenger side air mix damper position sensor circuit |
|
| B1437/-45 | Short in passenger side air mix damper position sensor circuit |
|
| B1441/E45 | Passenger side air mix damper control servomotor circuit |
|
WIRING DIAGRAM
CAUTION / NOTICE / HINT
Note
This DTC is stored even for damper link and damper lock, etc. Prior to inspection, confirm that there are no parts with mechanical problems.
PROCEDURE
READ VALUE USING GTS
Connect the GTS to the DLC3.
Turn the ignition switch to ON.
Turn the GTS on.
Operate the front passenger side temperature adjustment switch.
Enter the following menus: Body Electrical / Air Conditioner / Data List.
Check the value(s) by referring to the table below.
| Tester Display | Measurement Item/Range | Normal Condition | Diagnostic Note |
|---|---|---|---|
| Air Mix Damper Position A/M Damp Pos-P) |
Passenger side air mix damper position / Min.: -32.68%, Max.: 133.33% |
MAX. COLD: 0% MAX. HOT: 110% |
- |
| Air Mix Damper Target(P) | Passenger side air mix damper target position / Min.: -32.68%, Max.: 133.33% |
MAX. COLD: 0% MAX. HOT: 110% |
- |
| NG |
|
CHECK HARNESS AND CONNECTOR (NO. 4 AIR CONDITIONING RADIATOR DAMPER SERVO SUB-ASSEMBLY - AIR CONDITIONING CONTROL ASSEMBLY) Click here |
| OK |
|
CHECK FOR DTC
Clear the DTCs Click here.
Check the DTCs Click here.
Turn the GTS on.
| OK |
|---|
| DTC is not out put. |
| OK |
|
END |
| NG |
|
REPLACE AIR CONDITIONING CONTROL ASSEMBLY Click here |
CHECK HARNESS AND CONNECTOR (NO. 4 AIR CONDITIONING RADIATOR DAMPER SERVO SUB-ASSEMBLY - AIR CONDITIONING CONTROL ASSEMBLY)
Disconnect the D20 air conditioning control assembly.
Disconnect the A28 No. 4 air conditioning radiator damper servo sub-assembly (air mix (for front passenger side)).
Measure the resistance according to the value(s) in the table below.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| A28-1(VZ) - D20-13(S5) | Always | Below 1Ω |
| A28-3(GND) - D20-6(SG) | Always | Below 1Ω |
| A28-5(TP) - D20-3(TPPa) | Always | Below 1Ω |
| A28-6(COOL) - D20-12(AMCPa) | Always | Below 1Ω |
| A28-7(HOT) - D20-11(AMHPa) | Always | Below 1Ω |
| A28-1(VZ) - Body ground | Always | 10 kΩ or higher |
| A28-3(GND) - Body ground | Always | 10 kΩ or higher |
| A28-5(TP) - Body ground | Always | 10 kΩ or higher |
| A28-6(COOL) - Body ground | Always | 10 kΩ or higher |
| A28-7(HOT) - Body ground | Always | 10 kΩ or higher |
| NG |
|
REPAIR OR REPLACE HARNESS AND CONNECTOR |
| OK |
|
INSPECT NO. 4 AIR CONDITIONING RADIATOR DAMPER SERVO SUB-ASSEMBLY
Remove the No. 4 air conditioning radiator damper servo sub-assembly (air mix (for front passenger side)) Click here.
Potentiometer circuit inspection
Measure the resistance according to the value(s) in the table below.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| A28-1(VZ) - A28-3(GND) | Always | 4.2 to 7.8 kΩ |
| *a | Component without harness connected (No. 4 air Conditioning radiator damper servo sub-assembly) |
Measure the resistance according to the value(s) in the table below.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| A28-1(VZ) - A28-5(TP) | MAX. COOL position | 3.4 to 6.2 kΩ |
| A28-1(VZ) - A28-5(TP) | MAX. HOT position | 0.8 to 1.6 kΩ |
| *A | for LHD |
| *B | for RHD |
| *a | MAX. HOT |
| *b | MAX. COOL |
As the arm of the air mix control servo motor moves from the COOL side to the HOT side, the resistance decreases gradually without interruption.
Motor circuit inspection
When the terminal 6 (COOL) of the connector A28 is connected to the battery positive terminal, and terminal 7 (HOT) of the connector A28 is connected to the battery negative terminal, confirm that the arm smoothly rotates from HOT to COOL.
Tech Tips
Because the arm does not automatically stop at servo unit inspection, at inspection, turn off the power supply near COOL
When the terminal 7 (HOT) of the connector A28 is connected to the battery positive terminal, and terminal 6 (COOL) of the connector A28 is connected to the battery negative terminal, confirm that the arm smoothly rotates from COOL to HOT.
Tech Tips
Because the arm does not automatically stop at servo unit inspection, at inspection, turn off the power supply near HOT.
| OK |
|
REPLACE AIR CONDITIONING CONTROL ASSEMBLY Click here |
| NG |
|
REPLACE NO. 4 AIR CONDITIONING RADIATOR DAMPER SERVO SUB-ASSEMBLY (AIR MIX) Click here |