INSPECT REFRIGERANT PRESSURE
This method uses a refrigerant recovery unit set to locate problem areas. Read the refrigerant pressure when the test conditions are established.
Test conditions:
Doors are fully open.
The power switch is on (READY).
The A/C switch is on.
The temperature is set to max cool.
The blower speed is set to high.
Temperature at the air inlet with the air recirculation switch set at RECIRC is 30 to 35°C (86 to 95°F).
Normally functioning refrigeration system.
| Gauge Reading | ||||||
|---|---|---|---|---|---|---|
|
The A/C system periodically changes between normal and improper function due to moisture in the refrigerant system.
| *a | Low Pressure Side | *b | High Pressure Side |
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
| During operation, pressure on low pressure side cycles between normal and vacuum | Moisture in refrigeration system freezes at expansion valve orifice, causing temporary stop of cycle. However, when melted, normal state is restored. |
|
|
The A/C system does not function effectively due to insufficient refrigerant.
| *a | Low Pressure Side | *b | High Pressure Side |
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
|
Gas leakage from refrigeration system |
|
|
The A/C system does not function effectively due to poor circulation of the refrigerant.
| *a | Low Pressure Side | *b | High Pressure Side |
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
|
Refrigerant flow obstructed by dirt in condenser | Condenser clogged | Replace condenser |
The A/C system does not function or functions intermittently because the refrigerant does not circulate.
| *a | Low Pressure Side | *b | High Pressure Side |
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
|
|
Refrigerant does not circulate |
|
The A/C system does not function effectively due to the system being overcharged with refrigerant or insufficient cooling of the condenser.
| *a | Low Pressure Side | *b | High Pressure Side |
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
| Pressure extremely high on both low and high-pressure sides |
|
|
|
The A/C system does not function due to air in the refrigeration system.
CAUTION:
The low-pressure piping may be very hot and cause serious burns.
Note
These gauge indications occur when the refrigeration system opens and the system is charged with refrigerant without vacuum purging.
| *a | Low Pressure Side | *b | High Pressure Side |
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
|
Air in refrigeration system |
|
|
The A/C system does not function effectively due to an expansion valve malfunction.
| *a | Low Pressure Side | *b | High Pressure Side |
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
|
Problem with expansion valve |
|
Replace expansion valve |
The A/C system does not function due to a defective compressor.
| *a | Low Pressure Side | *b | High Pressure Side |
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
|
Internal leakage in compressor |
|
Repair or replace compressor |
Gauge readings (Reference):
| *a | Pressure on low-pressure side | *b | Blower HI Zone |
| *c | Blower LO Zone | *d | Pressure on high-pressure side |