INSPECT AIR CONDITIONING THERMISTOR ASSEMBLY
| *a | Component without harness connected (Air Conditioning Thermistor Assembly (Glass Temperature Sensor)) |
| *b | Heat Conduction Sheet |
| *c | Resistance (kΩ) |
| *d | Temperature (°C (°F)) |
For glass temperature sensor:
Remove the air conditioning thermistor assembly (glass temperature sensor).
Measure the resistance according to the value(s) in the table below.
| Standard Resistance | ||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Note
Hold the sensor only by its connector. Touching the sensor may change the resistance value.
When measuring, the sensor temperature must be the same as the ambient temperature.
Tech Tips
As the temperature increases, the resistance decreases (refer to the graph).
If the result is not as specified, replace the air conditioning thermistor assembly (glass temperature sensor).
| *a | Component without harness connected (Air Conditioning Thermistor Assembly (Glass Surroundings Temperature Sensor)) |
| *b | Heat Conduction Sheet |
| *c | Resistance (kΩ) |
| *d | Temperature (°C (°F)) |
For glass surroundings temperature sensor:
Remove the air conditioning thermistor assembly (glass surroundings temperature sensor).
Measure the resistance according to the value(s) in the table below.
| Standard Resistance | ||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Note
Hold the sensor only by its connector. Touching the sensor may change the resistance value.
When measuring, the sensor temperature must be the same as the ambient temperature.
Tech Tips
As the temperature increases, the resistance decreases (refer to the graph).
If the result is not as specified, replace the air conditioning thermistor assembly (glass surroundings temperature sensor).
| *a | Component without harness connected (Air Conditioning Thermistor Assembly (Humidity Sensor)) |
| *b | Heat Conduction Sheet |
| *c | Voltage (V) |
| *d | Relative Humidity (%) |
For humidity sensor:
Remove the air conditioning thermistor assembly (humidity sensor) with the connector still connected.
Turn the engine switch on (IG).
Measure the voltage according to the value(s) in the table below.
| Standard Voltage | ||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Note
Do not touch the sensor as body heat will affect the inspection results. When performing the inspection, hold the sensor by its connector.
Allow the sensor to acclimate to the ambient temperature and humidity before performing the inspection.
The specified voltages in the table above are based on inspections performed when the ambient temperature is 25°C (77°F).
Tech Tips
As the humidity increases, the voltage increases (refer to the graph).
If the result is not as specified, replace the air conditioning thermistor assembly (humidity sensor).