FRONT EVAPORATOR TEMPERATURE SENSOR INSPECTION


  1. INSPECT EVAPORATOR TEMPERATURE SENSOR


    1. A003T3TE66
      Text in Illustration
      *1

      Component without harness connected

      (Evaporator Temperature Sensor)

      *2 Sensing Portion
      *3 Resistance (kΩ)
      *4 Allowable Range
      *5 Temperature °C (°F)

      Measure the resistance according to the value(s) in the table below.

      Standard Resistance
      Tester Connection Condition Specified Condition
      z21-1 - z21-2 -10°C (14°F) 7.30 to 9.10 kΩ
      z21-1 - z21-2 -5°C (23°F) 5.65 to 6.95 kΩ
      z21-1 - z21-2 0°C (32°F) 4.40 to 5.35 kΩ
      z21-1 - z21-2 5°C (41°F) 3.40 to 4.15 kΩ
      z21-1 - z21-2 10°C (50°F) 2.70 to 3.25 kΩ
      z21-1 - z21-2 15°C (59°F) 2.14 to 2.58 kΩ
      z21-1 - z21-2 20°C (68°F) 1.71 to 2.05 kΩ
      z21-1 - z21-2 25°C (77°F) 1.38 to 1.64 kΩ
      z21-1 - z21-2 30°C (86°F) 1.11 to 1.32 kΩ

      Note


      • Hold the sensor only by its connector.Touching the sensor may change the resistance value.

      • When measuring, the sensor temperature must be the same as the ambient temperature.

      Tech Tips

      As the temperature increases, the resistance decreases (see the graph).

      If the resistance is not as specified, replace the evaporator temperature sensor.