INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET
Tech Tips
This is a method where a manifold gauge set is used to help locate the problem.
Read the manifold gauge pressure when the following conditions are met:
Test conditions:
Temperature at the air inlet with the switch set at RECIRC is 30 to 35°C (86 to 95°F).
The blower speed control switch position is at "HI".
The temperature control dial position is at "COOL".
The A/C switch is on.
Doors are fully open.
The power switch is in a position that enables the A/C compressor to run.
Normally functioning refrigeration system
| Pressure Side | Refrigerant Volume |
|---|---|
| Low | 0.15 to 0.25 MPa (1.5 to 2.5 kgf/cm2, 21 to 36 psi) |
| High | 1.37 to 1.57 MPa (13.9 to 16.0 kgf/cm2, 199 to 228 psi) |
Moisture is present in the refrigeration system.
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
| During operation, pressure on low pressure side cycles between normal and vacuum |
|
|
|
Insufficient cooling
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
|
Gas leaks from the refrigeration system |
|
|
Poor circulation of refrigerant
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
|
Refrigerant flow is obstructed by dirt inside the pipes of the condenser core | Receiver is clogged | Replace condenser |
Refrigerant does not circulate.
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
|
|
Refrigerant does not circulate |
|
Refrigerant is overcharged or cooling effectiveness of condenser is insufficient.
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
|
|
|
|
Air is present in the refrigeration system.
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
|
Air in system |
|
|
Expansion valve malfunction
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
|
Expansion valve may be stuck |
|
Check expansion valve |
Insufficient compressor compression
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
|
Internal leak in compressor |
|
Replace compressor |
Gauge readings (Reference)