AIR CONDITIONING PRESSURE SENSOR INSTALLATION


  1. INSTALL AIR CONDITIONING PRESSURE SENSOR


    1. Sufficiently apply compressor oil to a new air conditioning pressure sensor.

      Compressor oil
      ND-OIL 11 or equivalent

      Note


      • Keep the O-ring and O-ring fitting surfaces clean from dirt or any foreign matter.

      • Do not use any compressor oil other than ND-OIL 11 or equivalent. If any compressor oil other than ND-OIL 11 or equivalent is used, compressor motor insulation performance may decrease, resulting in a leakage of electric power.

    2. Install the new air conditioning pressure sensor.

      Torque:
      11 N*m  { 110 kgf*cm, 8 ft.*lbf }

      Note


      • Do not deform the piping.

      • Make sure to confirm that the piping does not disengage from the plastic clamp.

    3. Connect the connector.

  2. CHARGE AIR CONDITIONING SYSTEM WITH REFRIGERANT


    1. Perform vacuum purging using a vacuum pump or appropriate equipment.

    2. Charge the air conditioning system with refrigerant.

      Refrigerant type
      HFC-134a (R134a)
      A0043LPE11
      Text in Illustration
      *a Sub-cool System *b High Pressure
      *c Refrigerant Amount *d Standard charge amount
      *e Charge additional 100 g (3.5 oz.) *f Point where bubbles disappear
      *g Mean value in proper range *h Overcharged
      Standard charge amount
      440 to 500g (15.5 to 17.6oz.)
      SST
      09985-20010   ( 09985-02010, 09985-02050, 09985-02060, 09985-02070, 09985-02080, 09985-02090, 09985-02110, 09985-02130, 09985-02140, 09985-02150 )

      Note


      • Do not turn the A/C switch on before charging the air conditioning system with refrigerant. Doing so may cause the compressor to work without refrigerant, resulting in overheating of the compressor.

      • The refrigerant amount should be checked by quantity (weight).

      Tech Tips

      Ensure that sufficient refrigerant is available to recharge the system when using a refrigerant recovery unit. Refrigerant recovery units are not always able to recover 100% of the refrigerant from an air conditioning system.

  3. WARM UP COMPRESSOR


    1. Keep the A/C switch on for at least 2 minutes to warm up the compressor.

      Note

      To prevent damage to the compressor, be sure to warm up the compressor when turning the air conditioning on after removing and installing air conditioning system lines (including the compressor).

  4. INSPECT FOR REFRIGERANT LEAK


    1. After recharging the air conditioning system with refrigerant, inspect for refrigerant leaks using a halogen leak detector.

    2. Carry out the test under the following conditions:


      • Power switch off.

      • Secure good ventilation (the halogen leak detector may react to volatile gases which are not refrigerant, such as gasoline vapor and exhaust gas).

      • Repeat the inspection 2 or 3 times.

      • Measure the pressure to make sure that there is some refrigerant remaining in the air conditioning system.

        Pressure when the compressor is off: approx. 392 to 588 kPa (3.9 to 5.9 kgf/cm2, 57 to 85 psi)

    3. A0043GFE40
      Text in Illustration
      *1 Halogen Leak Detector
      *a Inspect for Leak

      Using a halogen leak detector, inspect for refrigerant leaks from the air conditioning system.

    4. A004341E08
      Text in Illustration
      *1 Halogen Leak Detector
      *2 Drain Hose

      Bring the halogen leak detector close to the drain hose with the detector power off, and then turn the detector on.

      Tech Tips


      • After the blower motor has stopped, leave the cooling unit for more than 15 minutes.

      • Bring the halogen leak detector sensor under the drain hose.

      • When bringing the halogen leak detector close to the drain hose, make sure that the halogen leak detector does not react to volatile gases. If it is not possible to avoid interference from volatile gases, the vehicle should be lifted up to allow checking for leaks.

    5. If a refrigerant leak is not detected from the drain hose, remove the blower motor control from the cooling unit. Insert the halogen leak detector sensor into the unit and check for a leak.

    6. Disconnect the pressure sensor connector and leave it for approximately 20 minutes. Bring the halogen leak detector close to the pressure sensor and check for a leak.

      Tech Tips

      When checking for leaks, the presence of oily dirt at a joint can indicate a leak.