REFRIGERANT ON-VEHICLE INSPECTION


  1. INSPECT REFRIGERANT VOLUME


    1. A01NFWN

      Check the sight glass on the air conditioning tube and accessory.


      1. Prepare the vehicle according to the chart below.

        Item Condition
        Vehicle door Fully open
        Temperature setting MAX COOL
        Blower speed HI
        A/C on
      2. Compare the sight glass to the following chart.

        Item Symptom Amount of Refrigerant Corrective Action
        1 Bubbles exist Insufficient*
        1. Check for gas leaks and repair if necessary

        2. Recharge with a proper amount of refrigerant

        2 No bubbles exist Empty, insufficient, or excessive Refer to 3 and 4
        3 No temperature difference between compressor inlet and outlet Empty or nearly empty
        1. Check for gas leaks and repair if necessary

        2. Evacuate the AC system and recharge with a proper amount of refrigerant

        4 Considerable temperature difference between compressor inlet and outlet Proper or excessive Refer to 5 and 6
        5 Immediately after air conditioning is turned off, refrigerant remains clear Excessive
        1. Recover refrigerant

        2. Evacuate the AC system and recharge with a proper amount of refrigerant

        6 Immediately after air conditioning is turned off, refrigerant foams and then becomes clear Proper -

        *: Bubbles in the sight glass with the vehicle's interior temperature above 35°C (95°F) can be considered normal if cooling is sufficient.

  2. INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET

    Tech Tips

    This is a method where a manifold gauge set is used to help locate the problem.


    1. Read the manifold gauge pressure when the following conditions are met:

      Test conditions:


      • Temperature at the air inlet with the switch set at RECIRC is 30 to 35°C (86 to 95°F).

      • The blower speed control switch position is at "HI".

      • The temperature control dial position is at "COOL".

      • The A/C switch is on.

      • Doors are fully open.

      • The power switch is in a position that enables the A/C compressor to run.


      1. A01NESW

        Normally functioning refrigeration system

        Gauge Reading
        Pressure Side Refrigerant Volume
        Low

        0.15 to 0.25 MPa (1.5 to 2.5 kgf/cm2, 21 to 36 psi)

        High

        1.37 to 1.57 MPa (13.9 to 16.0 kgf/cm2, 199 to 228 psi)

      2. Moisture is present in the refrigeration system.

        A01NHABE28
        Symptom Probable Cause Diagnosis Corrective Action
        During operation, pressure on low pressure side cycles between normal and vacuum
        • Moisture in the AC system will freeze at the expansion valve orifice, causing the refrigeration cycle to temporarily stop

        • After the system stops, and warms up again, the ice will melt and normal operation will be temporarily restored


        • Cooler dryer (integrated into condenser tank) in oversaturated state

        • Moisture in refrigeration system freezes at expansion valve orifice and blocks circulation of refrigerant


        1. Replace cooler dryer

        2. Remove moisture in system by repeatedly evacuating air

        3. Supply a proper amount of new refrigerant

      3. Insufficient cooling

        A01NEN3E13
        Symptom Probable Cause Diagnosis Corrective Action

        • Pressure is low on both low and high pressure sides

        • Bubbles are seen through sight glass continuously

        • Insufficient cooling performance

        Gas leaks from the refrigeration system
        • Insufficient refrigerant

        • Refrigerant leaking


        1. Check for gas leaks and repair if necessary

        2. Supply a proper amount of new refrigerant

        3. If the gauge indicates a pressure of close to 0, then it will be necessary to evacuate the system after repairing the leak

      4. Poor circulation of refrigerant

        A01NH1EE14
        Symptom Probable Cause Diagnosis Corrective Action

        • Pressure is low on both low and high pressure sides

        • Frost exists on pipe from condenser to unit

        Refrigerant flow is obstructed by dirt inside the pipes of the condenser core Receiver is clogged Replace condenser
      5. Refrigerant does not circulate.

        A01NF24E14
        Symptom Probable Cause Diagnosis Corrective Action

        • Vacuum is indicated on low pressure side and very low pressure is indicated on high pressure side

        • Frost or condensation is seen on piping on both sides of receiver/drier or expansion valve


        • Refrigerant flow is obstructed by moisture or dirt in refrigeration system

        • Refrigerant flow is disrupted by gas leaks internally through the expansion valve

        Refrigerant does not circulate
        1. Check expansion valve

        2. Replace expansion valve

        3. Replace condenser

        4. Evacuate air and supply a proper amount of new refrigerant

        5. For internal gas leaks at expansion valve, replace expansion valve

      6. Refrigerant is overcharged or cooling effectiveness of condenser is insufficient.

        A01NEDPE14
        Symptom Probable Cause Diagnosis Corrective Action

        • Pressure is too high on both low and high pressure sides

        • No air bubbles are seen through sight glass even when compressor is on


        • Unable to develop sufficient performance due to excessive use of refrigeration system

        • Cooling effectiveness of condenser is insufficient


        • Excessive refrigerant in cycle → excessive refrigerant was added during recharging

        • Condenser cooling effectiveness is insufficient → condenser fins are clogged at cooling fan


        1. Clean condenser

        2. Check the operation of the condenser cooling fan

        3. If 1 and 2 are normal state, check the amount of refrigerant and supply a proper amount of refrigerant

      7. Air is present in the refrigeration system.

        A01NGJKE06
        Symptom Probable Cause Diagnosis Corrective Action

        • Pressure is too high on both low and high pressure sides

        • The low pressure piping is too hot to touch

        • Bubbles can be seen through sight glass

        Air in system
        • Air present in refrigeration system

        • Insufficient vacuum purging


        1. Check compressor oil to see if it is dirty or insufficient

        2. Evacuate the system and recharge it with new or purified refrigerant

      8. Expansion valve malfunction

        A01NGK6E05
        Symptom Probable Cause Diagnosis Corrective Action

        • Pressure is too high on both low and high pressure sides

        • Frost or a large amount of condensation on piping on low pressure side

        Expansion valve may be stuck
        • Excessive refrigerant in low pressure piping

        • Expansion valve opened too wide

        Check expansion valve
      9. Insufficient compressor compression

        A01NDWUE05
        Symptom Probable Cause Diagnosis Corrective Action

        • Pressure is too high on both low and high pressure sides

        • Pressure is too low on high pressure side

        Internal leak in compressor
        • Low compression

        • Leak from a damaged valve, or parts may be broken

        Replace compressor

        Gauge readings (Reference)

        A01NDNQE31