DESCRIPTION
This DTC is stored when refrigerant pressure on the high pressure side is extremely low (0.19 MPa (2.0 kgf/cm2, 28 psi) or less) or extremely high (3.14 MPa (32.0 kgf/cm2, 455 psi) or more). The A/C pressure sensor is installed on the high pressure line. It detects refrigerant pressure to output a refrigerant pressure signal to the A/C amplifier. The A/C amplifier converts this signal to a pressure value according to the sensor characteristics to control the compressor.
| DTC No. | DTC Detection Condition | Trouble Area |
|---|---|---|
| B1423/23 |
|
|
WIRING DIAGRAM
INSPECTION PROCEDURE
PROCEDURE
CHECK HARNESS AND CONNECTOR (POWER SOURCE CIRCUIT)
| *1 | Front view of wire harness connector (to A/C Pressure Sensor) |
Disconnect the A/C pressure sensor connector.
Measure the voltage according to the value(s) in the table below.
| Standard Voltage | ||||||
|---|---|---|---|---|---|---|
|
| NG |
|
CHECK HARNESS AND CONNECTOR (A/C AMPLIFIER - A/C PRESSURE SENSOR) Click here |
| OK |
|
CHECK HARNESS AND CONNECTOR (GROUND CIRCUIT)
| *1 | Front view of wire harness connector (to A/C Pressure Sensor) |
Measure the resistance according to the value(s) in the table below.
| Standard Resistance | ||||||
|---|---|---|---|---|---|---|
|
| NG |
|
CHECK HARNESS AND CONNECTOR (A/C AMPLIFIER - A/C PRESSURE SENSOR) Click here |
| OK |
|
INSPECT A/C PRESSURE SENSOR (SENSOR SIGNAL CIRCUIT)
Reconnect the A/C pressure sensor connector.
| *1 | Component with harness connected (A/C Amplifier) |
Remove the A/C amplifier with the connectors still connected.
Measure the voltage according to the value(s) in the table below.
| Standard Voltage | ||||||
|---|---|---|---|---|---|---|
|
Tech Tips
If the voltage is not as specified, there may be a malfunction in the A/C amplifier, A/C pressure sensor or wire harness. It is also possible that the amount of refrigerant may not be appropriate.
| NG |
|
CHECK HARNESS AND CONNECTOR (A/C AMPLIFIER - A/C PRESSURE SENSOR) Click here |
| OK |
|
INSPECT A/C PRESSURE SENSOR (SENSOR SIGNAL CIRCUIT)
Measure the voltage when the following conditions are met:
| Item | Condition |
|---|---|
| Vehicle Doors | Fully open |
| Compressor speed | 5200 rpm |
| Temperature Setting | MAX COLD |
| Blower Speed | HI |
| A/C Switch | on |
| R/F Switch | RECIRCULATION |
| Interior Temperature | 25 to 35°C (77 to 95°F) |
Note
If refrigerant pressure on the high pressure line becomes extremely high during the inspection (if the voltage exceeds 4.84 V), the fail-safe function stops compressor operation. Therefore, measure the voltage before the fail-safe function operates.
It is necessary to measure the voltage over a period of time (approximately 10 minutes) because the problem symptom may recur after a while.
Tech Tips
When the outside air temperature is low (below -1.5°C (29.3°F)), the compressor stops due to signals from the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
| *1 | Component with harness connected (A/C Amplifier) |
Measure the voltage according to the value(s) in the table below.
| Standard Voltage | ||||||
|---|---|---|---|---|---|---|
|
| Result | ||||||||
|---|---|---|---|---|---|---|---|---|
|
| B |
|
PROCEED TO NEXT SUSPECTED AREA SHOWN IN PROBLEM SYMPTOMS TABLE Click here |
| C |
|
INSPECT COOLING FAN SYSTEM Click here |
| A |
|
REPLACE A/C AMPLIFIER Click here
CHECK HARNESS AND CONNECTOR (A/C AMPLIFIER - A/C PRESSURE SENSOR)
Disconnect the A/C amplifier connector.
| *1 | Front view of wire harness connector (to A/C Amplifier) |
| *2 | Front view of wire harness connector (to A/C Pressure Sensor) |
Measure the resistance according to the value(s) in the table below.
| Standard Resistance | |||||||||
|---|---|---|---|---|---|---|---|---|---|
|
| NG |
|
REPAIR OR REPLACE HARNESS OR CONNECTOR |
| OK |
|
REPLACE A/C AMPLIFIER Click here
CHECK HARNESS AND CONNECTOR (A/C AMPLIFIER - A/C PRESSURE SENSOR)
Disconnect the A/C amplifier connector.
| *1 | Front view of wire harness connector (to A/C Amplifier) |
| *2 | Front view of wire harness connector (to A/C Pressure Sensor) |
Measure the resistance according to the value(s) in the table below.
| Standard Resistance | |||||||||
|---|---|---|---|---|---|---|---|---|---|
|
| NG |
|
REPAIR OR REPLACE HARNESS OR CONNECTOR |
| OK |
|
REPLACE A/C AMPLIFIER Click here
CHECK HARNESS AND CONNECTOR (A/C AMPLIFIER - A/C PRESSURE SENSOR)
Disconnect the A/C amplifier connector.
| *1 | Front view of wire harness connector (to A/C Amplifier) |
| *2 | Front view of wire harness connector (to A/C Pressure Sensor) |
Measure the resistance according to the value(s) in the table below.
| Standard Resistance | |||||||||
|---|---|---|---|---|---|---|---|---|---|
|
| NG |
|
REPAIR OR REPLACE HARNESS OR CONNECTOR |
| OK |
|
CHECK FOR A/C SYSTEM LEAK
Install the manifold gauge set.
Recover the refrigerant from the A/C system using a refrigerant recovery unit.
Evacuate the A/C system and check that vacuum can be maintained.
| OK |
|---|
| Vacuum can be maintained in the A/C system. |
Tech Tips
If vacuum cannot be maintained in the A/C system, there may be a refrigerant leak. In this case, it is necessary to repair or replace the leaking part of the A/C system.
| NG |
|
REPAIR A/C SYSTEM LEAK Click here |
| OK |
|
CHARGE REFRIGERANT
Add an appropriate amount of refrigerant Click here.
| NEXT |
|
RECHECK FOR DTC
Recheck for the DTC when the following conditions are met:
| Item | Condition |
|---|---|
| Vehicle Doors | Fully open |
| Compressor speed | 5200 rpm |
| Temperature Setting | MAX COLD |
| Blower Speed | HI |
| A/C Switch | on |
| R/F Switch | RECIRCULATION |
| Interior Temperature | 25 to 35°C (77 to 95°F) |
Note
If refrigerant pressure on the high pressure line is excessive, this DTC will be stored. Therefore, it is necessary to measure the voltage over a period of time (approximately 10 minutes) because this DTC may be stored after the A/C has been operating for a while.
Tech Tips
When the outside air temperature is low (below -1.5°C (29.3°F)), the compressor stops due to signals from the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
| Result | ||||||
|---|---|---|---|---|---|---|
|
Note
If the DTC was stored due to an insufficient or excessive amount of refrigerant, the problem may have been solved after performing the previous step. However, the root cause of insufficient refrigerant may be refrigerant leaks. The root cause of excessive refrigerant may be adding refrigerant when the level was insufficient. Therefore, identify and repair any refrigerant leaks as necessary.
| B |
|
END |
| A |
|
INSPECT A/C PRESSURE SENSOR
Install the manifold gauge set.
Reconnect the A/C pressure sensor connector.
Turn the power switch on (IG).
| *1 | Component with harness connected (A/C Amplifier) |
Measure the voltage according to the value(s) in the table below.
| Standard Voltage | ||||||
|---|---|---|---|---|---|---|
|
| NG |
|
REPLACE A/C PRESSURE SENSOR Click here |
| OK |
|
REPLACE A/C AMPLIFIER Click here
REPAIR A/C SYSTEM LEAK
Identify the area where refrigerant leaks from Click here.
Repair the identified area of the A/C system.
Evacuate the A/C system.
| NEXT |
|
CHARGE REFRIGERANT Click here
INSPECT COOLING FAN SYSTEM
Check that the cooling fan(s) operates normally.
Tech Tips
Refer to Cooling Fan Circuit Click here.
| NG |
|
REPAIR COOLING FAN SYSTEM |
| OK |
|
CHARGE REFRIGERANT
Use a refrigerant recovery unit to recover refrigerant.
Evacuate the A/C system.
Add an appropriate amount of refrigerant Click here.
Tech Tips
If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the expansion valve, blocking the flow on the high pressure side. Therefore, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for DTCs.
| NEXT |
|
RECHECK FOR DTC
Recheck for the DTC when the following conditions are met:
| Item | Condition |
|---|---|
| Vehicle Doors | Fully open |
| Compressor speed | 5200 rpm |
| Temperature Setting | MAX COLD |
| Blower Speed | HI |
| A/C Switch | on |
| R/F Switch | RECIRCULATION |
| Interior Temperature | 25 to 35°C (77 to 95°F) |
Note
If refrigerant pressure on the high pressure line is excessive, this DTC will be stored. Therefore, it is necessary to measure the voltage over a period of time (approximately 10 minutes) because DTC may be stored after the A/C has been operating for a while.
Tech Tips
When the outside air temperature is low (below -1.5°C (29.3°F)), the compressor stops due to signals from the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the expansion valve, blocking the flow on the high pressure side. Therefore, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for the DTC. If the DTC is not output, it indicates that the cooler dryer in the condenser is not able to absorb moisture in the refrigerant. In this case, to complete the repair, it is necessary to replace the cooler dryer.
| Result | ||||||
|---|---|---|---|---|---|---|
|
| B |
|
REPLACE COOLER DRYER Click here |
| A |
|
REPLACE EXPANSION VALVE
Replace the expansion valve with a new or a known good one Click here.
Tech Tips
Replace the expansion valve with a new or a known good one because the expansion valve is either stuck or clogged.
| NEXT |
|
CHARGE REFRIGERANT
Add an appropriate amount of refrigerant Click here.
| NEXT |
|
RECHECK FOR DTC
Recheck for the DTC when the following conditions are met:
| Item | Condition |
|---|---|
| Vehicle Doors | Fully open |
| Compressor speed | 5200 rpm |
| Temperature Setting | MAX COLD |
| Blower Speed | HI |
| A/C Switch | on |
| R/F Switch | RECIRCULATION |
| Interior Temperature | 25 to 35°C (77 to 95°F) |
Note
If refrigerant pressure on the high pressure line is excessive, this DTC will be stored. Therefore, it is necessary to measure the voltage over a period of time (approximately 10 minutes) because this DTC may be stored after the A/C has been operating for a while.
Tech Tips
When the outside air temperature is low (below -1.5°C (29.3°F)), the compressor stops due to signals from the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
If refrigerant pressure is not normal after replacing the expansion valve with a new or a known good one, the condenser or pipes may be clogged with dirt, dust or other contaminants. In this case, clean or replace the condenser or pipes.
| Result | ||||||
|---|---|---|---|---|---|---|
|
| B |
|
REPLACE CONDENSER Click here |
| A |
|
END
REPLACE A/C PRESSURE SENSOR
Replace the A/C pressure sensor Click here.
Tech Tips
Since the A/C pressure sensor cannot be inspected while it is removed from the vehicle, replace the A/C pressure sensor with a new or a known good one and check that the condition returns to normal.
| NEXT |
|
RECHECK FOR DTC
Recheck for the DTC when the following conditions are met:
| Item | Condition |
|---|---|
| Vehicle Doors | Fully open |
| Compressor speed | 5200 rpm |
| Temperature Setting | MAX COLD |
| Blower Speed | HI |
| A/C Switch | on |
| R/F Switch | RECIRCULATION |
| Interior Temperature | 25 to 35°C (77 to 95°F) |
Note
If refrigerant pressure on the high pressure line is excessive, this DTC will be stored. Therefore, it is necessary to measure the voltage over a period of time (approximately 10 minutes) because this DTC may be stored after the A/C has been operating for a while.
Tech Tips
When the outside air temperature is low (below -1.5°C (29.3°F)), the compressor stops due to signals from the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
| Result | ||||||
|---|---|---|---|---|---|---|
|
| B |
|
REPLACE A/C AMPLIFIER Click here |
| A |
|
END