BLOWER RESISTOR (for Manual Air Conditioning System) INSPECTION


  1. INSPECT BLOWER RESISTOR

    A011A42E01
    Text in Illustration
    *1 Component without harness connected: (Blower resister)

    1. Check the resistance.


      1. Measure the resistance according to the value(s) in the table below.

        Standard Resistance
        Tester Connection Condition Specified Condition
        1 - 2 Always 1.53 to 1.75 Ω
        2 - 3 Always 3.01 to 3.47 Ω
        2 - 6 Always 0.44 to 0.50 Ω

        If the result is not as specified, replace the blower resistor.