VALVE BODY ASSEMBLY INSPECTION


  1. INSPECT SHIFT SOLENOID VALVE SL


    1. A01CD64E01

      Measure the resistance according to the value(s) in the table below.

      Standard Resistance
      Tester Connection Condition Specified Condition
      Solenoid Connector (SL) - Solenoid Body (SL) 20°C (68°F) 11 to 15 Ω

      If the value is not as specified, replace the shift solenoid valve.

    2. Connect a positive (+) battery lead to the terminal of the solenoid connector, and a negative (-) battery lead to the solenoid body, and check the operation of the valve.

      Note

      When using battery voltage during the inspection, do not bring the positive and negative tester probes too close to each other as a short circuit may occur.

      OK
      Valve moves and makes an operating sound.

      If the operation cannot be done as specified, replace the shift solenoid valve.

  2. INSPECT SHIFT SOLENOID VALVE SLT


    1. A01CB53E19

      Measure the resistance according to the value(s) in the table below.

      Standard Resistance
      Tester Connection Condition Specified Condition
      1 - 2 20°C (68°F) 5.0 to 5.6 Ω

      If the value is not as specified, replace the shift solenoid valve.

    2. Connect a positive (+) battery lead with a 21 W bulb to terminal 2 and a negative (-) battery lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

      Note

      When using battery voltage during the inspection, do not bring the positive and negative tester probes too close to each other as a short circuit may occur.

      OK
      Valve moves and makes an operating sound.

      If the operation cannot be done as specified, replace the shift solenoid valve.

  3. INSPECT SHIFT SOLENOID VALVE SLU


    1. A01CB53E20

      Measure the resistance according to the value(s) in the table below.

      Standard Resistance
      Tester Connection Condition Specified Condition
      1 - 2 20°C (68°F) 5.0 to 5.6 Ω

      If the value is not as specified, replace the shift solenoid valve.

    2. Connect a positive (+) battery lead with a 21 W bulb to terminal 2 and a negative (-) battery lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

      Note

      When using battery voltage during the inspection, do not bring the positive and negative tester probes too close to each other as a short circuit may occur.

      OK
      Valve moves and makes an operating sound.

      If the operation cannot be done as specified, replace the shift solenoid valve.

  4. INSPECT SHIFT SOLENOID VALVE SL1


    1. A01CB53E22

      Measure the resistance according to the value(s) in the table below.

      Standard Resistance
      Tester Connection Condition Specified Condition
      1 - 2 20°C (68°F) 5.0 to 5.6 Ω

      If the value is not as specified, replace the shift solenoid valve.

    2. Connect a positive (+) battery lead with a 21 W bulb to terminal 2 and a negative (-) battery lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

      Note

      When using battery voltage during the inspection, do not bring the positive and negative tester probes too close to each other as a short circuit may occur.

      OK
      Valve moves and makes an operating sound.

      If the operation cannot be done as specified, replace the shift solenoid valve.

  5. INSPECT SHIFT SOLENOID VALVE SL2


    1. A01CB53E21

      Measure the resistance according to the value(s) in the table below.

      Standard Resistance
      Tester Connection Condition Specified Condition
      1 - 2 20°C (68°F) 5.0 to 5.6 Ω

      If the value is not as specified, replace the shift solenoid valve.

    2. Connect a positive (+) battery lead with a 21 W bulb to terminal 2 and a negative (-) battery lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

      Note

      When using battery voltage during the inspection, do not bring the positive and negative tester probes too close to each other as a short circuit may occur.

      OK
      Valve moves and makes an operating sound.

      If the operation cannot be done as specified, replace the shift solenoid valve.

  6. INSPECT SHIFT SOLENOID VALVE SL3


    1. A01CB53E23

      Measure the resistance according to the value(s) in the table below.

      Standard Resistance
      Tester Connection Condition Specified Condition
      1 - 2 20°C (68°F) 5.0 to 5.6 Ω

      If the value is not as specified, replace the shift solenoid valve.

    2. Connect a positive (+) battery lead with a 21 W bulb to terminal 2 and a negative (-) battery lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

      Note

      When using battery voltage during the inspection, do not bring the positive and negative tester probes too close to each other as a short circuit may occur.

      OK
      Valve moves and makes an operating sound.

      If the operation cannot be done as specified, replace the shift solenoid valve.

  7. INSPECT SHIFT SOLENOID VALVE SL4


    1. A01CB53E24

      Measure the resistance according to the value(s) in the table below.

      Standard Resistance
      Tester Connection Condition Specified Condition
      1 - 2 20°C (68°F) 5.0 to 5.6 Ω

      If the value is not as specified, replace the shift solenoid valve.

    2. Connect a positive (+) battery lead with a 21 W bulb to terminal 2 and a negative (-) battery lead to terminal 1 of the solenoid valve connector, and check the operation of the valve.

      Note

      When using battery voltage during the inspection, do not bring the positive and negative tester probes too close to each other as a short circuit may occur.

      OK
      Valve moves and makes an operating sound.

      If the operation cannot be done as specified, replace the shift solenoid valve.