| DTC Code | DTC Name |
|---|---|
| B1423/23 | Pressure Sensor Circuit |
DESCRIPTION
This DTC is stored if refrigerant pressure on the high pressure side is extremely low (0.19 MPa (2.0 kgf/cm2, 28 psi) or less) or extremely high (3.14 MPa (32.0 kgf/cm2, 455 psi) or more). The air conditioning pressure sensor, which is installed on the pipe on the high pressure side to detect refrigerant pressure, sends a refrigerant pressure signal to the air conditioning amplifier assembly. The air conditioning amplifier assembly converts this signal to a pressure value according to the sensor characteristics and uses it to control the compressor.
| DTC No. | DTC Detection Condition | Trouble Area |
|---|---|---|
| B1423/23 |
|
|
WIRING DIAGRAM
| *a | Air Conditioning Pressure Sensor |
| *b | Air Conditioning Amplifier Assembly |
PROCEDURE
CHECK HARNESS AND CONNECTOR (POWER SOURCE CIRCUIT)
Disconnect the A47 air conditioning pressure sensor connector.
Measure the voltage according to the value(s) in the table below.
| Standard Voltage | ||||||
|---|---|---|---|---|---|---|
|
| NG |
|
CHECK HARNESS AND CONNECTOR (AIR CONDITIONING AMPLIFIER ASSEMBLY - AIR CONDITIONING PRESSURE SENSOR) Click here |
| OK |
|
CHECK HARNESS AND CONNECTOR (GROUND CIRCUIT)
Measure the resistance according to the value(s) in the table below.
| Standard Resistance | ||||||
|---|---|---|---|---|---|---|
|
| NG |
|
CHECK HARNESS AND CONNECTOR (AIR CONDITIONING AMPLIFIER ASSEMBLY - AIR CONDITIONING PRESSURE SENSOR) Click here |
| OK |
|
INSPECT AIR CONDITIONING PRESSURE SENSOR (SENSOR SIGNAL CIRCUIT)
Reconnect the A47 air conditioning pressure sensor connector.
| *a | Component with harness connected (Air Conditioning Amplifier Assembly) |
Remove the air conditioning amplifier assembly with the connectors still connected.
Measure the voltage according to the value(s) in the table below.
| Standard Voltage | ||||||
|---|---|---|---|---|---|---|
|
Tech Tips
If the measured voltage is not within the normal range, there may be a malfunction in the air conditioning amplifier assembly, air conditioning pressure sensor, or wire harness. It is also possible that the amount of refrigerant may not be appropriate.
| NG |
|
CHECK HARNESS AND CONNECTOR (AIR CONDITIONING AMPLIFIER ASSEMBLY - AIR CONDITIONING PRESSURE SENSOR) Click here |
| OK |
|
INSPECT AIR CONDITIONING PRESSURE SENSOR (SENSOR SIGNAL CIRCUIT)
Turn the power switch on (READY).
Measure the voltage when the following conditions are satisfied.
| Item | Condition |
|---|---|
| Vehicle Doors | Fully open |
| Temperature Setting | MAX COLD |
| Blower Speed | HI |
| A/C Switch | On |
| R/F Switch | Recirculation |
| Interior Temperature | 25 to 35°C (77 to 95°F) |
Note
If refrigerant pressure on the high pressure side becomes extremely high during the inspection (if the voltage exceeds 4.80 V), the fail-safe function stops compressor operation. Therefore, measure the voltage before the fail-safe operation.
It is necessary to measure the voltage for a certain amount of time (approximately 10 minutes) because the problem symptom may recur after a while.
Tech Tips
When the outside air temperature is low (below -1.5°C (29.3°F)), the compressor stops due to operation of the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
| *a | Component with harness connected (Air Conditioning Amplifier Assembly) |
Measure the voltage according to the value(s) in the table below.
| Standard Voltage | ||||||
|---|---|---|---|---|---|---|
|
| Result | ||||||||
|---|---|---|---|---|---|---|---|---|
|
| A |
|
REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY Click here |
| B |
|
PROCEED TO NEXT SUSPECTED AREA SHOWN IN PROBLEM SYMPTOMS TABLE Click here |
| C |
|
INSPECT COOLING FAN SYSTEM Click here |
CHECK HARNESS AND CONNECTOR (AIR CONDITIONING AMPLIFIER ASSEMBLY - AIR CONDITIONING PRESSURE SENSOR)
Disconnect the H54 air conditioning amplifier assembly connector.
Measure the resistance according to the value(s) in the table below.
| Standard Resistance | |||||||||
|---|---|---|---|---|---|---|---|---|---|
|
| OK |
|
REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY Click here |
| NG |
|
REPAIR OR REPLACE HARNESS OR CONNECTOR |
CHECK HARNESS AND CONNECTOR (AIR CONDITIONING AMPLIFIER ASSEMBLY - AIR CONDITIONING PRESSURE SENSOR)
Disconnect the H54 air conditioning amplifier assembly connector.
Measure the resistance according to the value(s) in the table below.
| Standard Resistance | |||||||||
|---|---|---|---|---|---|---|---|---|---|
|
| OK |
|
REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY Click here |
| NG |
|
REPAIR OR REPLACE HARNESS OR CONNECTOR |
CHECK HARNESS AND CONNECTOR (AIR CONDITIONING AMPLIFIER ASSEMBLY - AIR CONDITIONING PRESSURE SENSOR)
Disconnect the H54 air conditioning amplifier assembly connector.
Measure the resistance according to the value(s) in the table below.
| Standard Resistance | |||||||||
|---|---|---|---|---|---|---|---|---|---|
|
| NG |
|
REPAIR OR REPLACE HARNESS OR CONNECTOR |
| OK |
|
INSPECT FOR A/C SYSTEM LEAK
Install a manifold gauge set.
Recover the refrigerant from the A/C system using a refrigerant recovery unit.
Evacuate the A/C system and check that vacuum can be maintained in it.
| OK |
|---|
| Vacuum can be maintained in the A/C system. |
Tech Tips
If vacuum cannot be maintained in the A/C system, refrigerant may be leaking from it. In this case, it is necessary to repair or replace the leaking part of the A/C system.
| NG |
|
REPAIR A/C SYSTEM LEAK Click here |
| OK |
|
CHARGE SYSTEM WITH REFRIGERANT
Use a refrigerant recovery unit to recover refrigerant.
Evacuate the A/C system.
Add an appropriate amount of refrigerant Click here.
Tech Tips
If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the cooler expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for DTCs.
| NEXT |
|
RECHECK FOR DTC
Turn the power switch on (READY).
Recheck for DTCs when the following conditions are satisfied.
| Item | Condition |
|---|---|
| Vehicle Doors | Fully open |
| Temperature Setting | MAX COLD |
| Blower Speed | HI |
| A/C Switch | On |
| R/F Switch | Recirculation |
| Interior Temperature | 25 to 35°C (77 to 95°F) |
Note
If refrigerant pressure on the high pressure side becomes high, the DTC will be set. It is necessary to measure the voltage for a certain amount of time (approximately 10 minutes) because the DTC may be set after the A/C operates for a while.
Tech Tips
When the outside air temperature is low (below -1.5°C (29.3°F)), the compressor stops due to operation of the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
| Result | ||||||
|---|---|---|---|---|---|---|
|
Note
If the DTC was set due to an insufficient or excessive amount of refrigerant, the problem may have been solved after performing the previous step. However, the root cause of insufficient refrigerant may be refrigerant leaks. The root cause of excessive refrigerant may be adding refrigerant when the level was insufficient. Therefore, identify and repair the area where refrigerant leaks from as necessary.
| B |
|
END |
| A |
|
INSPECT AIR CONDITIONING PRESSURE SENSOR
Install a manifold gauge set.
Reconnect the A47 air conditioning pressure sensor connector.
Turn the power switch on (IG).
| *a | Component with harness connected (Air Conditioning Amplifier Assembly) |
Measure the voltage according to the value(s) in the table below.
| Standard Voltage | ||||||
|---|---|---|---|---|---|---|
|
| OK |
|
REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY Click here |
| NG |
|
REPLACE AIR CONDITIONING PRESSURE SENSOR Click here |
REPAIR A/C SYSTEM LEAK
Identify the area where refrigerant leaks from Click here.
Repair the identified area of the A/C system.
Evacuate the A/C system.
| NEXT |
|
CHARGE SYSTEM WITH REFRIGERANT Click here |
INSPECT COOLING FAN SYSTEM
Check that the cooling fan(s) operates normally.
Tech Tips
Refer to cooling fan system Click here.
| NG |
|
REPAIR COOLING FAN SYSTEM |
| OK |
|
CHARGE SYSTEM WITH REFRIGERANT
Use a refrigerant recovery unit to recover refrigerant.
Evacuate the A/C system.
Add an appropriate amount of refrigerant Click here.
Tech Tips
If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the cooler expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for DTCs.
| NEXT |
|
RECHECK FOR DTC
Turn the power switch on (READY).
Recheck for DTCs when the following conditions are satisfied.
| Item | Condition |
|---|---|
| Vehicle Doors | Fully open |
| Temperature Setting | MAX COLD |
| Blower Speed | HI |
| A/C Switch | On |
| R/F Switch | Recirculation |
| Interior Temperature | 25 to 35°C (77 to 95°F) |
Note
If refrigerant pressure on the high pressure side becomes high, the DTC will be set. It is necessary to measure the voltage for a certain amount of time (approximately 10 minutes) because the DTC may be set after the air conditioning operates for a while.
Tech Tips
When the outside air temperature is low (below -1.5°C (29.3°F)), the compressor stops due to operation of the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the cooler expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for DTCs. If DTCs are not output after this work, it indicates that the cooler dryer in the cooler condenser assembly is not able to absorb moisture in the refrigerant cycle. It is necessary to replace the cooler dryer in order to complete the repair.
| Result | ||||||
|---|---|---|---|---|---|---|
|
| B |
|
REPLACE COOLER CONDENSER ASSEMBLY Click here |
| A |
|
REPLACE COOLER EXPANSION VALVE
Replace the cooler expansion valve with a new one Click here.
Tech Tips
Replace the cooler expansion valve with a new one because the cooler expansion valve is either stuck or clogged.
| NEXT |
|
CHARGE SYSTEM WITH REFRIGERANT
Use a refrigerant recovery unit to recover refrigerant.
Evacuate the A/C system.
Add an appropriate amount of refrigerant Click here.
Tech Tips
If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the cooler expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for DTCs.
| NEXT |
|
RECHECK FOR DTC
Turn the power switch on (READY).
Recheck for DTCs when the following conditions are satisfied.
| Item | Condition |
|---|---|
| Vehicle Doors | Fully open |
| Temperature Setting | MAX COLD |
| Blower Speed | HI |
| A/C Switch | On |
| R/F Switch | Recirculation |
| Interior Temperature | 25 to 35°C (77 to 95°F) |
Note
If refrigerant pressure on the high pressure side becomes high, the DTC will be set. It is necessary to measure the voltage for a certain amount of time (approximately 10 minutes) because the DTC may be set after the air conditioning operates for a while.
Tech Tips
When the outside air temperature is low (below -1.5°C (29.3°F)), the compressor stops due to operation of the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
If refrigerant pressure is not normal after replacing the cooler expansion valve with a normal one, the cooler condenser assembly or pipes may be clogged due to dirt, dust or other foreign matter. In this case, clean or replace the cooler condenser assembly or pipes.
| Result | ||||||
|---|---|---|---|---|---|---|
|
| A |
|
END |
| B |
|
CLEAN OR REPLACE COOLER CONDENSER ASSEMBLY OR PIPE |