PROCEDURE
INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET
Tech Tips
The following examples show the readings of a manifold gauge set and the corresponding air conditioning system problems.
Read the manifold gauge pressure when the following conditions are met:
Doors are fully open.
The power switch is on (READY).
The A/C switch is on.
The temperature is set to max cool.
The blower speed is set to high.
Temperature at the air inlet with recirculate selected is 30 to 35°C (86 to 95°F).
| *a | LO |
| *b | HI |
Normally functioning air conditioning system
| Pressure Side | Refrigerant Volume |
|---|---|
| Low | 150 to 250 kPa (1.5 to 2.5 kgf/cm2, 22 to 36 psi) |
| High | 1420 to 1620 kPa (14.5 to 16.5 kgf/cm2, 206 to 235 psi) |
Abnormally functioning air conditioning system
| *a | LO |
| *b | HI |
During operation, pressure on low pressure side cycles between normal and vacuum
| Symptom | Air conditioning system periodically cools and then fails to cool |
| Probable Cause | Moisture in air conditioning system freezes at expansion valve orifice, causing refrigerant to temporarily stop circulating |
| After system stops and warms up again, ice melts and normal operation is temporarily restored | |
| Diagnosis | Accumulator and accessory assembly saturated with moisture |
| Moisture in air conditioning system is freezing at expansion valve orifice and blocking circulation of refrigerant | |
| Corrective Actions | Replace accumulator and accessory assembly |
| Remove moisture by repeatedly evacuating air from air conditioning system | |
| Recharge air conditioning system with proper amount of new or purified refrigerant |
Tech Tips
For the example above, moisture is present in the air conditioning system.
| *a | LO |
| *b | HI |
Pressure is low on both low and high pressure sides
| Symptom | Air conditioning system does not cool effectively |
| Insufficient cooling performance | |
| Probable Cause | Refrigerant leaks from air conditioning system |
| Diagnosis | Insufficient refrigerant |
| Refrigerant leaking | |
| Corrective Actions | Check for refrigerant leaks and repair if necessary |
| Recharge air conditioning system with proper amount of new or purified refrigerant | |
| If gauges indicate pressure of close to 0, then it is necessary to evacuate air conditioning system after repairing leaks |
Tech Tips
For the example above, there is insufficient refrigerant.
| *a | LO |
| *b | HI |
Pressure is too high on both low and high pressure sides
| Symptom | Air conditioning system does not cool effectively |
| Frost or large amount of condensation on piping on low pressure side | |
| Probable Cause | Expansion valve may be stuck open or metering refrigerant incorrectly |
| Diagnosis | Excessive refrigerant in low pressure piping |
| Expansion valve open too wide | |
| Corrective Actions | Replace expansion valve |
Tech Tips
For the example above, there is an expansion valve malfunction.
| *a | LO |
| *b | HI |
Pressure is too high on both low and high pressure sides or pressure is too low on high pressure side
| Symptom | Air conditioning system does not cool effectively |
| Probable Cause | Internal leak in compressor |
| Diagnosis | Low compression |
| Leak from damaged valve or other compressor component | |
| Corrective Actions | Replace compressor |
Tech Tips
For the example above, there is insufficient compressor compression.
Gauge readings (Reference)
| *a | Pressure on Low Pressure Side kPa (kgf/cm2, psi) |
*b | Pressure on High Pressure Side kPa (kgf/cm2, psi) |
| *c | Blower High Zone | *d | Blower Low Zone |