CHECK AIR CONDITIONING AMPLIFIER ASSEMBLY
Disconnect the F58 air conditioning amplifier assembly connector.
Measure the voltage and resistance according to the value(s) in the table below.
Tech Tips
Measure the values on the wire harness side with the connector disconnected.
| Terminal No. (Symbol) | Wiring Color | Terminal Description | Condition | Specified Condition |
|---|---|---|---|---|
| F58-2 (IG+) - F58-4 (GND) | B - W-B | Power source (IG) | Power switch on (IG) | 11 to 14 V |
| F58-2 (IG+) - F58-4 (GND) | B - W-B | Power source (IG) | Power switch off | Below 1 V |
| F58-1 (B) - F58-4 (GND) | V - W-B | Auxiliary battery power supply | Power switch off | 11 to 14 V |
| F58-4 (GND) - Body ground | W-B - Body ground | Ground | Always | Below 1 Ω |
Reconnect the F58 air conditioning amplifier assembly connector.
Measure the voltage and check for pulses according to the value(s) in the table below.
| Terminal No. (Symbol) | Wiring Color | Terminal Description | Condition | Specified Condition |
|---|---|---|---|---|
| F58-5 (RDFG) - F58-4 (GND) | W - W-B | Rear window defogger signal | Power switch on (IG), rear window defogger switch off | 11 to 14 V |
| F58-5 (RDFG) - F58-4 (GND) | W - W-B | Rear window defogger signal | Power switch on (IG), rear window defogger switch on | Below 1 V |
| F58-14 (LIN1) - F58-4 (GND) | BE - W-B | LIN communication line | Power switch on (IG) | Pulse generation |
CHECK AIR CONDITIONING CONTROL ASSEMBLY
Disconnect the F52 air conditioning control assembly connector.
Measure the voltage and resistance according to the value(s) in the table below.
Tech Tips
Measure the values on the wire harness side with the connector disconnected.
| Terminal No. (Symbol) | Wiring Color | Terminal Description | Condition | Specified Condition |
|---|---|---|---|---|
| F52-8 (IG+) - F52-1 (GND) | LG - W-B | Power source (IG) | Power switch on (IG) | 11 to 14 V |
| F52-8 (IG+) - F52-1 (GND) | LG - W-B | Power source (IG) | Power switch off | Below 1 V |
| F52-1 (GND) - Body ground | W-B - Body ground | Ground | Always | Below 1 Ω |
Reconnect the F52 air conditioning control assembly connector.
Check for pulses according to the value(s) in the table below.
| Terminal No. (Symbol) | Wiring Color | Terminal Description | Condition | Specified Condition |
|---|---|---|---|---|
| F52-6 (LIN1) - F52-1 (GND) | BE - W-B | LIN communication line | Power switch on (IG) | Pulse generation |