| DTC Code | DTC Name |
|---|---|
| B1423 | Open in Pressure Sensor Circuit / Abnormal Refrigerant Pressure |
DESCRIPTION
This DTC is stored if refrigerant pressure on the high pressure side is extremely low (176 kPa (1.8 kgf/cm2, 26 psi) or less) or extremely high (3025 kPa (30.8 kgf/cm2, 439 psi) or more). The air conditioning tube and accessory assembly (air conditioner pressure sensor), which is installed on the pipe on the high pressure side to detect refrigerant pressure, sends a refrigerant pressure signal to the air conditioning amplifier assembly. The air conditioning amplifier assembly converts this signal to a pressure value according to the sensor characteristics and uses it to control the compressor.
| DTC No. | Detection Item | DTC Detection Condition | Trouble Area | Memory | Note |
|---|---|---|---|---|---|
| B1423 | Open in Pressure Sensor Circuit / Abnormal Refrigerant Pressure |
|
|
- | - |
Tech Tips
The air conditioning amplifier assembly stores the DTC of the respective malfunction if it has occurred for the period of time indicated in the brackets.
WIRING DIAGRAM
| *a | Air Conditioning Tube and Accessory Assembly (Air Conditioner Pressure Sensor) |
| *b | Air Conditioning Amplifier Assembly |
CAUTION / NOTICE / HINT
Note
When the auxiliary battery is disconnected or the air conditioning amplifier assembly is replaced, be sure to perform servo motor initialization.
Tech Tips
If DTC B1423 and B14B8 are output at the same time, troubleshoot for DTC B14B8 first.
PROCEDURE
CHECK AIR CONDITIONER PRESSURE SENSOR (POWER SOURCE CIRCUIT)
| *a | Front view of wire harness connector (to Air Conditioner Pressure Sensor) |
Disconnect the air conditioner pressure sensor connector.
Measure the voltage according to the value(s) in the table below.
| Standard Voltage | ||||||
|---|---|---|---|---|---|---|
|
| Result | |||
|---|---|---|---|
|
| NG |
|
CHECK HARNESS AND CONNECTOR (AIR CONDITIONING AMPLIFIER ASSEMBLY - AIR CONDITIONING TUBE AND ACCESSORY ASSEMBLY [AIR CONDITIONER PRESSURE SENSOR]) Click here |
| OK |
|
CHECK AIR CONDITIONER PRESSURE SENSOR (SENSOR SIGNAL CIRCUIT)
| *a | Component with harness connected (Air Conditioning Amplifier Assembly) |
Remove the air conditioning amplifier assembly with the connectors still connected.
Measure the voltage according to the value(s) in the table below.
| Standard Voltage | ||||||
|---|---|---|---|---|---|---|
|
Tech Tips
If the measured voltage is not within the normal range, there may be a malfunction in the air conditioning amplifier assembly, air conditioner pressure sensor, or wire harness. It is also possible that the amount of refrigerant may not be appropriate.
| Result | |||
|---|---|---|---|
|
| NG |
|
CHECK HARNESS AND CONNECTOR (AIR CONDITIONING AMPLIFIER ASSEMBLY - AIR CONDITIONING TUBE AND ACCESSORY ASSEMBLY [AIR CONDITIONER PRESSURE SENSOR]) Click here |
| OK |
|
CHECK AIR CONDITIONER PRESSURE SENSOR (SENSOR SIGNAL CIRCUIT)
Measure the voltage when the following conditions are satisfied.
| Item | Condition |
|---|---|
| Vehicle Doors | Fully open |
| Temperature Setting | MAX COLD |
| Blower Speed | Hi |
| A/C Switch | On |
| R/F Switch | Recirculation |
| Interior Temperature | 25 to 35°C (77 to 95°F) |
Note
If refrigerant pressure on the high pressure side becomes extremely high during the inspection (if the voltage exceeds 4.8 V), the fail-safe function stops compressor operation. Therefore, measure the voltage before the fail-safe operation.
It is necessary to measure the voltage for a certain amount of time (approximately 10 minutes) because the problem symptom may recur after a while.
Tech Tips
When the outside air temperature is low (below -1.5°C [29.3°F]), the compressor stops due to operation of the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
| *a | Component with harness connected (Air Conditioning Amplifier Assembly) |
Measure the voltage according to the value(s) in the table below.
| Standard Voltage | ||||||
|---|---|---|---|---|---|---|
|
| Result | ||||||||
|---|---|---|---|---|---|---|---|---|
|
| A |
|
REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY Click here |
| B |
|
PROCEED TO NEXT SUSPECTED AREA SHOWN IN PROBLEM SYMPTOMS TABLE Click here |
| C |
|
CHECK COOLING FAN SYSTEM Click here |
CHECK HARNESS AND CONNECTOR (AIR CONDITIONING AMPLIFIER ASSEMBLY - AIR CONDITIONING TUBE AND ACCESSORY ASSEMBLY [AIR CONDITIONER PRESSURE SENSOR])
Disconnect the I50 air conditioning amplifier assembly connector.
Disconnect the A18 air conditioning tube and accessory assembly (air conditioner pressure sensor) connector.
Measure the resistance according to the value(s) in the table below.
| Standard Resistance | |||||||||
|---|---|---|---|---|---|---|---|---|---|
|
| Result | |||
|---|---|---|---|
|
| OK |
|
REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY Click here |
| NG |
|
REPAIR OR REPLACE HARNESS OR CONNECTOR |
CHECK COOLING FAN SYSTEM
Check that the cooling fan(s) operates normally.
| Result | |||
|---|---|---|---|
|
| NG |
|
GO TO COOLING FAN SYSTEM Click here |
| OK |
|
CHARGE SYSTEM WITH REFRIGERANT
Use a refrigerant recovery unit to recover refrigerant.
Evacuate the air conditioning system.
Add an appropriate amount of refrigerant.
for HFC-134a (R134a):
for HFO-1234yf (R1234yf):
Tech Tips
If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for DTC.
| Result | ||
|---|---|---|
|
| NEXT |
|
CHECK FOR DTC
Check for DTC when the following conditions are satisfied.
| Item | Condition |
|---|---|
| Vehicle Doors | Fully open |
| Temperature Setting | MAX COLD |
| Blower Speed | Hi |
| A/C Switch | On |
| R/F Switch | Recirculation |
| Interior Temperature | 25 to 35°C (77 to 95°F) |
Note
If refrigerant pressure on the high pressure side becomes high, the DTC will be set. It is necessary to measure the voltage for a certain amount of time (approximately 10 minutes) because the DTC may be set after the air conditioning operates for a while.
Tech Tips
When the outside air temperature is low (below -1.5°C [29.3°F]), the compressor stops due to operation of the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for DTC. If the DTC is not output after this work, it indicates that the cooler dryer in the condenser is not able to absorb moisture in the refrigerant cycle. It is necessary to replace the cooler dryer in order to complete the repair.
| Result | ||||||
|---|---|---|---|---|---|---|
|
| A |
|
REPLACE COOLER CONDENSER ASSEMBLY Click here |
| B |
|
REPLACE COOLER EXPANSION VALVE
Replace the cooler expansion valve with a new one.
Tech Tips
Replace the cooler expansion valve with a new one because the expansion valve is either stuck or clogged.
| Result | ||
|---|---|---|
|
| NEXT |
|
CHARGE SYSTEM WITH REFRIGERANT
Use a refrigerant recovery unit to recover refrigerant.
Evacuate the air conditioning system.
Add an appropriate amount of refrigerant.
for HFC-134a (R134a):
for HFO-1234yf (R1234yf):
Tech Tips
If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for DTC.
| Result | ||
|---|---|---|
|
| NEXT |
|
CHECK FOR DTC
Check for DTC when the following conditions are satisfied.
| Item | Condition |
|---|---|
| Vehicle Doors | Fully open |
| Temperature Setting | MAX COLD |
| Blower Speed | Hi |
| A/C Switch | On |
| R/F Switch | Recirculation |
| Interior Temperature | 25 to 35°C (77 to 95°F) |
Note
If refrigerant pressure on the high pressure side becomes high, the DTC will be set. It is necessary to measure the voltage for a certain amount of time (approximately 10 minutes) because the DTC may be set after the air conditioning operates for a while.
Tech Tips
When the outside air temperature is low (below -1.5°C [29.3°F]), the compressor stops due to operation of the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
If refrigerant pressure is not normal after replacing the expansion valve with a normal one, the condenser or pipes may be clogged due to dirt, dust or other foreign matter. In this case, clean or replace the condenser or pipes.
| Result | ||||||
|---|---|---|---|---|---|---|
|
| A |
|
END (COOLER EXPANSION VALVE IS DEFECTIVE) |
| B |
|
CLEAN OR REPLACE COOLER CONDENSER ASSEMBLY |
CHECK HARNESS AND CONNECTOR (AIR CONDITIONING AMPLIFIER ASSEMBLY - AIR CONDITIONING TUBE AND ACCESSORY ASSEMBLY [AIR CONDITIONER PRESSURE SENSOR])
Disconnect the I50 air conditioning amplifier assembly connector.
Disconnect the A18 air conditioning tube and accessory assembly (air conditioner pressure sensor) connector.
Measure the resistance according to the value(s) in the table below.
| Standard Resistance | |||||||||
|---|---|---|---|---|---|---|---|---|---|
|
| Result | |||
|---|---|---|---|
|
| NG |
|
REPAIR OR REPLACE HARNESS OR CONNECTOR |
| OK |
|
CHECK FOR AIR CONDITIONING SYSTEM LEAK
Install a manifold gauge set.
Recover the refrigerant from the air conditioning system using a refrigerant recovery unit.
Evacuate the air conditioning system and check that vacuum can be maintained in it.
Tech Tips
If vacuum cannot be maintained in the air conditioning system, refrigerant may be leaking from it. In this case, it is necessary to repair or replace the leaking part of the air conditioning system.
| Result | ||||||
|---|---|---|---|---|---|---|
|
| B |
|
REPAIR AIR CONDITIONING SYSTEM LEAK Click here |
| A |
|
CHARGE SYSTEM WITH REFRIGERANT
Use a refrigerant recovery unit to recover refrigerant.
Evacuate the air conditioning system.
Add an appropriate amount of refrigerant.
for HFC-134a (R134a):
for HFO-1234yf (R1234yf):
Tech Tips
If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for DTC.
| Result | ||
|---|---|---|
|
| NEXT |
|
CHECK FOR DTC
Check for DTC when the following conditions are satisfied.
| Item | Condition |
|---|---|
| Vehicle Doors | Fully open |
| Temperature Setting | MAX COLD |
| Blower Speed | Hi |
| A/C Switch | On |
| R/F Switch | Recirculation |
| Interior Temperature | 25 to 35°C (77 to 95°F) |
Note
If refrigerant pressure on the high pressure side becomes high, the DTC will be set. It is necessary to measure the voltage for a certain amount of time (approximately 10 minutes) because the DTC may be set after the air conditioning operates for a while.
If the DTC was stored due to an insufficient or excessive amount of refrigerant, the problem may have been solved after performing the previous step. However, the root cause of insufficient refrigerant may be refrigerant leaks. The root cause of excessive refrigerant may be adding refrigerant when the level was insufficient. Therefore, identify and repair the area where refrigerant leaks from as necessary.
Tech Tips
When the outside air temperature is low (below -1.5°C [29.3°F]), the compressor stops due to operation of the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
| Result | ||||||
|---|---|---|---|---|---|---|
|
| A |
|
END |
| B |
|
CHECK AIR CONDITIONER PRESSURE SENSOR
Install a manifold gauge set.
Turn the power switch on (IG).
| *a | Component with harness connected (Air Conditioning Amplifier Assembly) |
Measure the voltage according to the value(s) in the table below.
| Standard Voltage | ||||||
|---|---|---|---|---|---|---|
|
| Result | |||
|---|---|---|---|
|
| NG |
|
REPLACE AIR CONDITIONING TUBE AND ACCESSORY ASSEMBLY (AIR CONDITIONER PRESSURE SENSOR) Click here |
| OK |
|
CHECK FOR DTC
Check for DTC when the following conditions are satisfied.
| Item | Condition |
|---|---|
| Vehicle Doors | Fully open |
| Temperature Setting | MAX COLD |
| Blower Speed | Hi |
| A/C Switch | On |
| R/F Switch | Recirculation |
| Interior Temperature | 25 to 35°C (77 to 95°F) |
Note
If refrigerant pressure on the high pressure side becomes high, the DTC will be set. It is necessary to measure the voltage for a certain amount of time (approximately 10 minutes) because the DTC may be set after the air conditioning operates for a while.
If the DTC was stored due to an insufficient or excessive amount of refrigerant, the problem may have been solved after performing the previous step. However, the root cause of insufficient refrigerant may be refrigerant leaks. The root cause of excessive refrigerant may be adding refrigerant when the level was insufficient. Therefore, identify and repair the area where refrigerant leaks from as necessary.
Tech Tips
When the outside air temperature is low (below -1.5°C [29.3°F]), the compressor stops due to operation of the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
| Result | ||||||
|---|---|---|---|---|---|---|
|
| A |
|
END |
| B |
|
REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY Click here |
REPAIR AIR CONDITIONING SYSTEM LEAK
Identify the area where refrigerant leaks from.
for HFC-134a (R134a):
for HFO-1234yf (R1234yf):
Repair the identified area of the air conditioning system.
Evacuate the air conditioning system.
| Result | ||
|---|---|---|
|
| NEXT |
|
CHARGE SYSTEM WITH REFRIGERANT for HFC-134a (R134a): CHARGE SYSTEM WITH REFRIGERANT Click here |