AIR CONDITIONING AMPLIFIER ASSEMBLY
Disconnect the air conditioning amplifier assembly I50 connector.
Measure the resistance and voltage according to the value(s) in the table below.
Tech Tips
Check from the rear of the connector while it is connected to the air conditioning amplifier assembly.
| Terminal No. (Symbol) |
Wiring Color | Terminal Description | Condition | Specified Condition |
|---|---|---|---|---|
| I50-1 (IG+) - Body ground | SB - Body ground | Power source (IG) | Power switch on (IG) | 11 to 14 V |
| Power switch off | Below 1 V | |||
| I50-14 (GND) - Body ground | W-B - Body ground | Ground for main power supply | Always | Below 1 Ω |
| I50-21 (B) - Body ground | GR - Body ground | Power source (Back-up) | Power switch off | 11 to 14 V |
Reconnect the air conditioning amplifier assembly I50 connector.
Measure the resistance, voltage and waveform according to the value(s) in the table below.
Tech Tips
Check from the rear of the connector while it is connected to the air conditioning amplifier assembly.
| Terminal No. (Symbol) |
Wiring Color | Terminal Description | Condition | Specified Condition |
|---|---|---|---|---|
| I50-3 (PTC2) - I50-14 (GND)*1 | GR - W-B | Quick heater assembly operation signal |
|
Below 1 V |
|
11 to 14 V | |||
| I50-4 (ECOS) - Body ground | R - Body ground | Integration control and panel assembly (ECO mode switch) signal | Power switch on (IG) Integration control and panel assembly (ECO mode switch) on |
Below 1 V |
| Power switch on (IG) Intergration control and panel assembly (ECO mode switch) off |
11 to 14 V | |||
| I50-5 (TAM) - I50-13 (SG-2)*2 | L - G | Ambient temperature sensor signal | Power switch on (IG) (do not start the engine and electric motor) Ambient temperature 10 °C (50 °F) |
1.8 to 2.4 V |
| Power switch on (IG) (do not start the engine and electric motor) Ambient temperature 15 °C (59 °F) |
1.65 to 2.15 V | |||
| Power switch on (IG) (do not start the engine and electric motor) Ambient temperature 20 °C (68 °F) |
1.5 to 1.95 V | |||
| Power switch on (IG) (do not start the engine and electric motor) Ambient temperature 25°C (77°F) |
1.35 to 1.75 V | |||
| Power switch on (IG) (do not start the engine and electric motor) Ambient temperature 30 °C (86 °F) |
1.2 to 1.55 V | |||
| Power switch on (IG) (do not start the engine and electric motor) Ambient temperature 35 °C (95 °F) |
1.0 to 1.4 V | |||
| Power switch on (IG) (do not start the engine and electric motor) Ambient temperature 40 °C (104 °F) |
0.85 to 1.25 V | |||
| Power switch on (IG) (do not start the engine and electric motor) Ambient temperature 45 °C (113 °F) |
0.75 to 1.10 V | |||
| Power switch on (IG) (do not start the engine and electric motor) Ambient temperature 50 °C (122 °F) |
0.8 to 1.0 V | |||
| I50-9 (PRE) - I50-10 (S5-3) | BE - B | Air conditioner pressure sensor signal | Engine running Air conditioning system operating Refrigerant pressure: Abnormal pressure (higher than 3025 kPa [30.8 kgf/cm2, 439 psi]) |
4.73 V or higher |
| Engine running Air conditioning system operating Refrigerant pressure: Abnormal pressure (below 176 kPa [1.8 kgf/cm2, 26 psi]) |
Below 0.62 V | |||
| Engine running Air conditioning system operating Refrigerant pressure: Normal pressure (below 3025 kPa [30.8 kgf/cm2, 439 psi] and higher than 176 kPa [1.8 kgf/cm2, 26 psi]) |
0.62 to 4.73 V | |||
| I50-10 (S5-3) - Body ground | B - Body ground | Ground for air conditioner pressure sensor, ambient temperature sensor, air conditioning lock sensor | Always | Below 1 Ω |
| I50-11 (CANH) | B (for LHD) P (for RHD) |
CAN communication line | - | - |
| I50-12 (CANL) | W | CAN communication line | - | - |
| I50-13 (SG-2) - Body ground | G - Body ground | Ground for ambient temperature sensor signal | Always | Below 1 Ω |
| I50-19 (PTC3) - I50-14 (GND)*1 | R - W-B | Quick heater assembly operation signal |
|
Below 1 V |
|
11 to 14 V | |||
| I50-22 (BLW) - Body ground | R - Body ground | Blower motor speed control signal | Power switch on (IG) Blower switch LO |
Pulse generation (See Waveform 1) |
| I50-27 (IDH) - I50-14 (GND) | W - W-B | Inverter with converter assembly current over signal |
|
Below 1 V |
|
4.75 to 5.25 V | |||
| I50-29 (TR) - I50-34 (SG-1) | GR - V | Room temperature sensor signal | Power switch on (IG) Cabin temperature: 25°C (77°F) |
1.8 to 2.2 V |
| Power switch on (IG) Cabin temperature: 40°C (104°F) |
1.2 to 1.6 V | |||
| I50-34 (SG-1) - Body ground | V - Body ground | Ground for room temperature sensor | Always | Below 1 Ω |
| I50-37 (LIN1) - Body ground | B - Body ground | LIN communication signal | Power switch on (IG) | Pulse generation |
| I50-40 (PTC1) - I50-14 (GND)*1 | B - W-B | Quick heater assembly operation signal |
|
Below 1 V |
|
11 to 14 V | |||
| z2-2 (BUS G) - Body ground | - | Ground for BUS IC | Always | Below 1 V |
| z2-3 (BUS) - z2-2 (BUS G) | - | BUS IC control signal | Power switch on (IG) | Pulse generation (See Waveform 1) |
| z2-4 (B BUS) - z2-2 (BUS G) | - | Power supply for BUS IC | Always | 11 to 14 V |
| z2-5 (SGA) - Body ground | GR - Body ground | Ground for evaporator temperature sensor | Always | Below 1 V |
| z2-6 (TEA) - z2-5 (SGA) | GR - GR | Evaporator temperature sensor signal | Power switch on (IG) Evaporator temperature: 0°C (32°F) |
1.7 to 2.1 V |
| z2-6 (TEA) - z2-5 (SGA) | GR - GR | Evaporator temperature sensor signal | Power switch on (IG) Evaporator temperature: 15°C (59°F) |
0.9 to 1.3 V |
*1: w/ PTC Heater
*2: Using a thermometer, to detects the ambient temperature around the installation area of the thermistor assembly (ambient temperature sensor) is installed
Waveform 1:
| Item | Content |
|---|---|
| Terminal No. | I50-22 (BLW) - Body ground |
| Tool Setting | 1 V/DIV., 500 μs/DIV. |
| Vehicle Condition | Power switch on (IG) Blower switch LO |
Waveform 2:
| Item | Content |
|---|---|
| Terminal No. | z2-3 (BUS) - z2-2 (BUS G) |
| Tool Setting | 2 V/DIV., 2 ms/DIV. |
| Vehicle Condition | Power switch on (IG) |
AIR CONDITIONING CONTROL ASSEMBLY
Disconnect the I13 air conditioning control assembly connector.
Measure the resistance and voltage according to the value(s) in the table below.
Tech Tips
Check from the rear of the connector while it is connected to the air conditioning control assembly.
| Terminal No. (Symbol) |
Wiring Color | Terminal Description | Condition | Specified Condition |
|---|---|---|---|---|
| I13-5 (ACC) - I13-14 (GND) | W - W-B | Power source (ACC) | Power switch on (ACC) | 11 to 14 V |
| Power switch off | Below 1 V | |||
| I13-7 (+B) - I13-14 (GND) | L - W-B | Power source (Back-up) | Power switch off | 11 to 14 V |
| I13-8 (IG+) - I13-14 (GND) | LG - W-B | Power source (IG) | Power switch on (IG) | 11 to 14 V |
| Power switch off | Below 1 V | |||
| I13-14 (GND) - Body ground | W-B - Body ground | Ground for center cluster module control assembly | Always | Below 1 Ω |
Reconnect the I13 air conditioning control assembly connector.
Measure the waveform according to the value(s) in the table below.
Tech Tips
Check from the rear of the connector while it is connected to the air conditioning control assembly.
| Terminal No. (Symbol) |
Wiring Color | Terminal Description | Condition | Specified Condition |
|---|---|---|---|---|
| I13-6 (LIN1) - I13-14 (GND) | B - W-B | LIN communication signal | Power switch on (IG) | Pulse generation |