Click here

REFRIGERANT(for HFO-1234yf(R1234yf)) ON-VEHICLE INSPECTION

Click here
Click here

PROCEDURE


  1. Click here

    INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET

    Tip:

    The following examples show the readings of a manifold gauge set and the corresponding air conditioning system problems.


    1. Remove the cool air intake duct seal.

      Click here

    2. Read the manifold gauge pressure when the following conditions are met:


      • Doors are fully open.

      • The engine is idling.

      • The A/C switch is on.

      • The temperature is set to max cool.

      • The blower speed is set to high.

      • Temperature at the air inlet with recirculate selected is 30 to 35°C (86 to 95°F).


      1. A0020ICC01
        *a LO
        *b HI

        Normally functioning air conditioning system

        Table 1. Gauge Reading
        Pressure Side Refrigerant Volume
        Low

        150 to 250 kPa (1.5 to 2.5 kgf/cm2, 22 to 36 psi)

        High

        1370 to 1570 kPa (14.0 to 16.0 kgf/cm2, 199 to 228 psi)

      2. Abnormally functioning air conditioning system


        1. A0022EEC10
          *a LO
          *b HI

          During operation, pressure on low pressure side cycles between normal and vacuum

          Symptom Air conditioning system periodically cools and then fails to cool
          Probable Cause Moisture in air conditioning system freezes at expansion valve orifice, causing refrigerant to temporarily stop circulating
          After system stops and warms up again, ice melts and normal operation is temporarily restored
          Diagnosis Cooler dryer (integrated into condenser tank) saturated with moisture
          Moisture in air conditioning system is freezing at expansion valve orifice and blocking circulation of refrigerant
          Corrective Actions Replace cooler dryer
          Remove moisture by repeatedly evacuating air from air conditioning system
          Recharge air conditioning system with proper amount of new or purified refrigerant
          Tip:

          For the example above, moisture is present in the air conditioning system.

        2. A0020WZC10
          *a LO
          *b HI

          Pressure is low on both low and high pressure sides

          Symptom Air conditioning system does not cool effectively
          Insufficient cooling performance
          Probable Cause Refrigerant leaks from air conditioning system
          Diagnosis Insufficient refrigerant
          Refrigerant leaking
          Corrective Actions Check for refrigerant leaks and repair if necessary
          Recharge air conditioning system with proper amount of new or purified refrigerant
          If gauges indicate pressure of close to 0, then it is necessary to evacuate air conditioning system after repairing leaks
          Tip:

          For the example above, there is insufficient refrigerant.

        3. A0020N1C10
          *a LO
          *b HI

          Pressure is low on both low and high pressure sides

          Symptom Air conditioning system does not cool effectively
          Frost exists on pipe from condenser to evaporator unit
          Probable Cause Refrigerant flow is obstructed by dirt inside pipes of condenser core
          Diagnosis Condenser is clogged
          Corrective Actions Replace condenser
          Tip:

          For the example above, there is poor circulation of refrigerant.

        4. A002251C10
          *a LO
          *b HI

          Vacuum is indicated on low pressure side and very low pressure is indicated on high pressure side

          Symptom Air conditioning system does not cool effectively (System may cool occasionally)
          Frost or condensation is seen on piping on both sides of receiver/dryer or expansion valve
          Probable Cause Refrigerant flow is obstructed by moisture or dirt in air conditioning system
          Expansion valve is stuck closed
          Diagnosis Refrigerant does not circulate
          Corrective Actions Replace expansion valve
          Replace condenser
          Evacuate air conditioning system and recharge with proper amount of new or purified refrigerant
          Tip:

          For the example above, the refrigerant does not circulate.

        5. A002183C10
          *a LO
          *b HI

          Pressure is too high on both low and high pressure sides

          Symptom Air conditioning system does not cool effectively
          Probable Cause Unable to provide sufficient performance due to excessive amount of refrigerant
          Cooling effectiveness of condenser is insufficient
          Diagnosis Excessive amount of refrigerant in air conditioning system because excessive refrigerant was added during recharging
          Cooling effectiveness of condenser is insufficient because condenser fins are clogged or cooling fan is faulty
          Corrective Actions Clean condenser
          Check operation of condenser cooling fan
          If condenser is clean and fan operation is normal, check amount of refrigerant and recharge air conditioning system with proper amount of new or purified refrigerant
          Tip:

          For the example above, the air conditioning system is overcharged or cooling effectiveness of condenser is insufficient.

        6. A0022ZWC09
          *a LO
          *b HI

          Pressure is too high on both low and high pressure sides

          Symptom Air conditioning system does not cool
          The low pressure piping is too hot to touch
          Probable Cause Air in air conditioning system
          Diagnosis Air present in air conditioning system
          Insufficient vacuum purging when evacuating air conditioning system
          Corrective Actions Replace cooler dryer
          Check compressor oil to see if it is dirty or insufficient
          Evacuate air conditioning system and recharge it with new or purified refrigerant
          Note:

          These gauge indications occur when the air conditioning system has been left open and then recharged without evacuating the system.

          Tip:

          For the example above, air is present in the air conditioning system.

        7. A0021SVC10
          *a LO
          *b HI

          Pressure is too high on both low and high pressure sides

          Symptom Air conditioning system does not cool effectively
          Frost or large amount of condensation on piping on low pressure side
          Probable Cause Expansion valve may be stuck open or metering refrigerant incorrectly
          Diagnosis Excessive refrigerant in low pressure piping
          Expansion valve open too wide
          Corrective Actions Replace expansion valve
          Tip:

          For the example above, there is an expansion valve malfunction.

        8. A0020C7C09
          *a LO
          *b HI

          Pressure is too high on both low and high pressure sides or pressure is too low on high pressure side

          Symptom Air conditioning system does not cool effectively
          Probable Cause Internal leak in compressor
          Diagnosis Low compression
          Leak from damaged valve or other compressor component
          Corrective Actions Replace compressor
          Tip:

          For the example above, there is insufficient compressor compression.

      3. A0022CCC04
        *a

        Pressure on Low Pressure Side kPa (kgf/cm2, psi)

        *b

        Pressure on High Pressure Side kPa (kgf/cm2, psi)

        *c Blower High Zone *d Blower Low Zone

        Gauge readings (Reference)

    3. Install the cool air intake duct seal.

      Click here