REFRIGERANT ON-VEHICLE INSPECTION

PROCEDURE


  1. INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET


    1. This method uses a manifold gauge set to locate problem areas. Read the manifold gauge pressure when these conditions are established.

      Test conditions:


      • Temperature at the air inlet with the switch set at RECIRC is 30 to 35°C (86 to 95°F).

      • Engine is running at 1500 rpm.

      • All doors are fully open.

      • Blower speed control switch is at HI.

      • A/C switch is on.

      Gauge readings (Reference).

      A01WVITE02

      1. A01WRZJ

        Normally functioning refrigeration system

        Gauge Reading
        Pressure Side Refrigerant Volume
        Low

        0.15 to 0.25 MPa (1.5 to 2.5 kgf/cm2)

        High

        1.37 to 1.57 MPa (14 to 16 kgf/cm2)

      2. The A/C system periodically changes between normal and improper function due to moisture in the refrigerant system.

        A01WUIV
        Symptoms Probable Cause Diagnosis Corrective Actions
        During operation, pressure on low pressure side cycles between normal and vacuum Moisture in refrigeration system freezes at expansion valve orifice, causing temporary stop of cycle. However, when melted, normal state is restored.

        - Dryer is overly saturated

        - Moisture in refrigeration system freezes at expansion valve orifice and blocks refrigerant circulation

        1. Replace cooler dryer

        2. Remove moisture from cycle by repeatedly evacuating air

        3. Supply appropriate volume of new refrigerant

      3. The A/C system does not function effectively due to insufficient refrigerant.

        A01WSCW
        Symptoms Probable Cause Diagnosis Corrective Actions

        - Pressure low on both low and high pressure sides

        - Cooling performance insufficient

        Gas leakage from refrigeration system

        - Insufficient refrigerant

        - Refrigerant leakage

        1. Check for gas leakage and repair if necessary

        2. Supply appropriate volume of new refrigerant

        3. If indicated pressure value close to 0 when connected to gauge, create vacuum after inspecting and repairing the location of leakage

      4. The A/C system does not function effectively due to poor circulation of the refrigerant.

        A01WV3V
        Symptoms Probable Cause Diagnosis Corrective Actions

        - Pressure low on both low and high pressure sides

        - Frost exists on piping from condenser to A/C unit

        Refrigerant flow obstructed by dirt in condenser Condenser clogged Replace condenser
      5. The A/C system does not function or functions intermittently because the refrigerant does not circulate.

        A01WPEU
        Symptoms Probable Cause Diagnosis Corrective Actions

        - Vacuum indicated on low pressure side, and extremely low pressure indicated on high pressure side

        - Frost or condensation seen on piping on both sides of condenser or expansion valve

        - Refrigerant flow obstructed by moisture or dirt in refrigeration system

        - Refrigerant flow obstructed by gas leakage from expansion valve

        Refrigerant does not circulate

        1. Check expansion valve refrigerant

        2. Clean expansion valve by blowing air

        3. Replace condenser

        4. Evacuate air and charge appropriate volume of new refrigerant

        5. For gas leakage from expansion valve, replace expansion valve

      6. The A/C system does not function effectively due to overcharged refrigerant or insufficient cooling of the condenser.

        A01WVIA
        Symptoms Probable Cause Diagnosis Corrective Actions
        Pressure extremely high on both low and high-pressure sides

        - Excessive refrigerant

        - Cooling performance of condenser insufficient

        - Condenser is dirty

        - Condenser fan motor is malfunctioning

        - Excessive refrigerant

        1. Clean condenser

        2. Check condenser fan motor operation

        3. If 1 and 2 normal, check the amount of refrigerant and supply appropriate volume of refrigerant

      7. The A/C system does not function due to air in the refrigeration system.

        CAUTION:

        The low-pressure piping may be very hot and cause serious burns.

        A01WVRYE32
        *1 HINT: These gauge indications occur when the refrigeration system opens and the refrigerant is charged without vacuum purging
        Symptoms Probable Cause Diagnosis Corrective Actions

        - Pressure extremely high on both low and high-pressure sides

        - Low-pressure piping is too hot to touch

        Air in refrigeration system

        - Air in refrigeration system

        - Vacuum purging insufficient

        1. Check if compressor oil is dirty or insufficient

        2. Evacuate air and charge new refrigerant

      8. The A/C system does not function effectively due to an expansion valve malfunction.

        A01WV6Y
        Symptoms Probable Cause Diagnosis Corrective Actions

        - Pressure extremely high on both low and high-pressure sides

        - Frost or condensation on piping on low-pressure side

        Problem with expansion valve

        - Excessive refrigerant in low pressure piping

        - Expansion valve too wide open

        Replace expansion valve
      9. The A/C system does not function due to a defective compressor.

        A01WVQ3
        Symptoms Probable Cause Diagnosis Corrective Actions

        - Pressure extremely high on low-pressure sides

        - Pressure extremely low on high pressure side

        Internal leakage in compressor

        - Compression failure

        - Leakage from damaged valve or broken sliding parts

        Repair or replace compressor