PROCEDURE
INSPECT NO. 1 PRESSURE SWITCH
| *a | Component without harness connected (No. 1 Pressure Switch) |
| *b | Low Pressure Side |
| *c | On (Below 1.0 Ω) |
| *d | High Pressure Side |
| *e | Off (10 kΩ or higher) |
Install a manifold gauge set.
Connect the positive (+) lead from the ohmmeter to terminal 1 and the negative (-) lead to terminal 2.
Check the resistance between terminals when refrigerant pressure is charged as shown in the illustration.
If operation is not as specified, replace the No. 1 pressure switch.
INSPECT AIR CONDITIONING PRESSURE SENSOR
Install a manifold gauge set.
Disconnect the connector from the air conditioning pressure sensor.
| *a | Component without harness connected (Air Conditioning Pressure Sensor) |
| *b | Voltage |
| *c | Refrigerant Pressure |
Connect the positive (+) lead of a DC 5 V power source to terminal 3 and the negative (-) lead to terminal 1.
Connect the positive (+) lead of the voltmeter to terminal 2 and the negative (-) lead to terminal 1.
Measure the voltage according to the value(s) in the table below.
| Standard Voltage | ||||||
|---|---|---|---|---|---|---|
|
If the result is not as specified, replace the air conditioning pressure sensor.