DESCRIPTION
The operation of the compressor with motor assembly is stopped and a DTC is stored if the rotation load is too large or too small while the compressor with motor assembly is operating.
Possible causes are refrigerant leaks, overcharged refrigerant, insufficient cooling because of a condenser fan circuit malfunction, or compressor lock.
| DTC No. | DTC Detection Condition | Trouble Area |
|---|---|---|
| B1476/76 | Motor rotation load while the compressor is operating is too large or too small. |
|
INSPECTION PROCEDURE
CAUTION:
Wear electrically insulated gloves and pull out the service plug grip before inspection as procedures may require disconnecting high-voltage connectors. Be sure to carry the removed service plug grip because other workers may install it by mistake.
Do not touch the high-voltage connectors or terminals for 10 minutes after the service plug grip is removed.
Note
After turning the power switch off, waiting time may be required before disconnecting the cable from the negative (-) auxiliary battery terminal. Therefore, make sure to read the disconnecting the cable from the negative (-) auxiliary battery terminal notices before proceeding with work Click here.
The hybrid control system and air conditioning system output DTCs separately. Inspect DTCs following the diagnosis procedure for the hybrid control system first if any DTCs from those systems are output simultaneously.
PROCEDURE
CHECK CAN COMMUNICATION SYSTEM
Using the Techstream to check if the CAN communication system is functioning normally.
| Result | ||||||
|---|---|---|---|---|---|---|
|
| B |
|
GO TO CAN COMMUNICATION SYSTEM Click here |
| A |
|
PERFORM ACTIVE TEST USING TECHSTREAM
Connect the Techstream to the DLC3.
Turn the power switch on (IG).
Turn the Techstream on.
Enter the following menus: Powertrain / Engine and ECT / Active Test.
Check the operation by referring to the table below.
| Tester Display | Test Part | Control Range | Diagnostic Note |
|---|---|---|---|
| Control the Electric Cooling Fan | Electric cooling fan | OFF, ON | - |
| NG |
|
GO TO COOLING FAN SYSTEM Click here |
| OK |
|
CHECK REFRIGERANT PRESSURE
Install a manifold gauge set Click here.
Read the manifold gauge pressure when the following conditions are established.
Prepare the vehicle according to the chart below.
| Item | Condition |
|---|---|
| Vehicle Doors | All fully open |
| Temperature Setting | MAX COLD |
| Blower Speed | HI |
| A/C switch | ON |
| R/F Switch | RECIRCULATION (30 to 35°C (86 to 95°F)) |
| Standard Pressure |
|---|
| Low pressure side |
| 150 to 250 kPa (1.5 to 2.5 kgf/cm2, 22 to 36 psi) |
| High pressure side |
| 1370 to 1570 kPa (14.0 to 16.0 kgf/cm2, 199 to 228 psi) |
| NG |
|
CHARGE REFRIGERANT Click here |
| OK |
|
REPLACE COMPRESSOR WITH MOTOR ASSEMBLY Click here