REFRIGERANT(for HFC-134a(R134a)) ON-VEHICLE INSPECTION

PROCEDURE


  1. INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET

    Tech Tips

    The following examples show the readings of a manifold gauge set and the corresponding air conditioning system problems.


    1. Read the manifold gauge pressure when the following conditions are met:


      • Temperature at the air inlet with recirculate selected is 30 to 35°C (86 to 95°F).

      • The blower speed is set to high.

      • The temperature is set to max cool.

      • The A/C switch is on.

      • Doors are fully open.

      • The power switch is on (READY).


      1. B001MLM

        Normally functioning air conditioning system.

        Gauge Reading
        Pressure Side Refrigerant Volume
        Low

        0.15 to 0.25 MPa (1.5 to 2.5 kgf/cm2, 21 to 36 psi)

        High

        1.37 to 1.57 MPa (14 to 16 kgf/cm2, 199 to 228 psi)

      2. Moisture is present in the air conditioning system.

        A00501LE53
        *1 Condition: Air conditioning system periodically cools and then fails to cool.
        Symptom Probable Cause Diagnosis Corrective Actions
        During operation, pressure on low pressure side cycles between normal and vacuum
        • Moisture in air conditioning system freezes at the expansion valve orifice, causing refrigerant to temporarily stop circulating

        • After the system stops, and warms up again, ice melts and normal operation is temporarily restored


        • Cooler dryer (integrated into condenser tank) saturated with moisture

        • Moisture in the air conditioning system freezes at expansion valve orifice and blocks circulation of refrigerant


        1. Replace cooler dryer

        2. Remove moisture by repeatedly evacuating air from the air conditioning system

        3. Recharge the air conditioning system with the proper amount of new or purified refrigerant

      3. Insufficient refrigerant

        A004WZ2E33
        *1 Condition: Air conditioning system does not cool effectively.
        Symptom Probable Cause Diagnosis Corrective Actions

        • Pressure is low on both low and high pressure sides

        • Insufficient cooling performance

        Refrigeration leaks from the system
        • Insufficient refrigerant

        • Refrigerant leaking


        1. Check for refrigerant leaks and repair if necessary

        2. Recharge the air conditioning system with the proper amount of new or purified refrigerant

        3. If the gauges indicate pressure of close to 0, then it is necessary to evacuate air conditioning system after repairing the leak

      4. Poor circulation of refrigerant

        A004VXOE33
        *1 Condition: Air conditioning system does not cool effectively.
        Symptom Probable Cause Diagnosis Corrective Actions

        • Pressure is low on both low and high pressure sides

        • Frost exists on pipe from condenser to evaporator unit

        Refrigerant flow is obstructed by dirt inside the pipes of the condenser core Condenser is clogged Replace condenser
      5. Refrigerant does not circulate.

        A004VQGE32
        *1 Condition: Air conditioning system does not cool. (System may cool occasionally.)
        Symptom Probable Cause Diagnosis Corrective Actions

        • Vacuum is indicated on low pressure side and very low pressure is indicated on high pressure side

        • Frost or condensation is seen on piping on both sides of receiver/dryer or expansion valve


        • Refrigerant flow is obstructed by moisture or dirt in air conditioning system

        • Expansion valve is stuck closed

        Refrigerant does not circulate
        1. Replace expansion valve

        2. Replace condenser

        3. Evacuate air conditioning system and supply the proper amount of new or purified refrigerant

      6. Air conditioning system is overcharged or cooling effectiveness of condenser is insufficient.

        A004XVEE35
        *1 Condition: Air conditioning system does not cool effectively.
        Symptom Probable Cause Diagnosis Corrective Actions
        Pressure is too high on both low and high pressure sides
        • Unable to develop sufficient performance due to excessive amount of refrigerant

        • Cooling effectiveness of condenser is insufficient


        • Excessive amount of refrigerant in air conditioning system → excessive refrigerant was added during recharging

        • Condenser cooling effectiveness is insufficient → condenser fins are clogged or cooling fan is faulty


        1. Clean condenser

        2. Check the operation of condenser cooling fan

        3. If 1 and 2 are normal, check the amount of refrigerant and recharge the air conditioning system with the proper amount of new or purified refrigerant

      7. Air is present in the air conditioning system.

        A004VWFE44
        *1 Condition: Air conditioning system does not cool.
        *2 NOTE: These gauge indications occur when the air conditioning system has been left open and then recharged without evacuating the system
        Symptom Probable Cause Diagnosis Corrective Actions

        • Pressure is too high on both low and high pressure sides

        • The low pressure piping is too hot to touch

        Air in air conditioning system
        • Air present in air conditioning system

        • Insufficient vacuum purging when evacuating the air conditioning system


        1. Replace cooler drier

        2. Check compressor oil to see if it is dirty or insufficient

        3. Evacuate the air conditioning system and recharge it with new or purified refrigerant

      8. Expansion valve malfunction

        A004W4FE30
        *1 Condition: Air conditioning system does not cool effectively.
        Symptom Probable Cause Diagnosis Corrective Actions

        • Pressure is too high on both low and high pressure sides

        • Frost or a large amount of condensation on piping on low pressure side

        Expansion valve may be stuck open or metering refrigerant incorrectly
        • Excessive refrigerant in low pressure piping

        • Expansion valve open too wide

        Replace expansion valve
      9. Insufficient compressor compression

        A004XKTE29
        *1 Condition: Air conditioning system does not cool.
        Symptom Probable Cause Diagnosis Corrective Actions

        • Pressure is too high on both low and high pressure sides

        • Pressure is too low on high pressure side

        Internal leak in compressor
        • Low compression

        • Leak from a damaged valve or other compressor component

        Replace compressor

        Gauge readings (Reference)

        A004Z68E03