PROCEDURE
INSPECT REFRIGERANT PRESSURE
This method uses a refrigerant recovery unit set to locate problem areas. Read the refrigerant pressure when the test conditions are established.
Test conditions:
Temperature at the air inlet with the air recirculation switch set at RECIRC is 30 to 35°C (86 to 95°F).
Engine is running at 1500 rpm.
All doors are fully open.
Blower speed control switch is set to HI.
A/C switch is on.
Gauge readings (Reference):
| *a | Pressure on low-pressure side | *b | Blower HI Zone |
| *c | Blower LO Zone | *d | Pressure on high-pressure side |
Normally functioning refrigeration system.
| Gauge Reading | ||||||
|---|---|---|---|---|---|---|
|
The A/C system periodically changes between normal and improper function due to moisture in the refrigerant system.
| *a | Low Pressure Side | *b | High Pressure Side |
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
| During operation, pressure on low pressure side cycles between normal and vacuum | Moisture in refrigeration system freezes at expansion valve orifice, causing temporary stop of cycle. However, when melted, normal state is restored. |
|
|
The A/C system does not function effectively due to insufficient refrigerant.
| *a | Low Pressure Side | *b | High Pressure Side |
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
|
Gas leakage from refrigeration system |
|
|
The A/C system does not function effectively due to poor circulation of the refrigerant.
| *a | Low Pressure Side | *b | High Pressure Side |
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
|
Refrigerant flow obstructed by dirt in condenser | Condenser clogged | Replace condenser |
The A/C system does not function or functions intermittently because the refrigerant does not circulate.
| *a | Low Pressure Side | *b | High Pressure Side |
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
|
|
Refrigerant does not circulate |
|
The A/C system does not function effectively due to the system being overcharged with refrigerant or insufficient cooling of the condenser.
| *a | Low Pressure Side | *b | High Pressure Side |
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
| Pressure extremely high on both low and high-pressure sides |
|
|
|
The A/C system does not function due to air in the refrigeration system.
CAUTION:
The low-pressure piping may be very hot and cause serious burns.
Note
These gauge indications occur when the refrigeration system opens and the system is charged with refrigerant without vacuum purging.
| *a | Low Pressure Side | *b | High Pressure Side |
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
|
Air in refrigeration system |
|
|
The A/C system does not function effectively due to an expansion valve malfunction.
| *a | Low Pressure Side | *b | High Pressure Side |
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
|
Problem with expansion valve |
|
Replace expansion valve |
The A/C system does not function due to a defective compressor.
| *a | Low Pressure Side | *b | High Pressure Side |
| Symptom | Probable Cause | Diagnosis | Corrective Action |
|---|---|---|---|
|
Internal leakage in compressor |
|
Repair or replace compressor |