AIR CONDITIONING SYSTEM(for Manual Air Conditioning System) DATA LIST / ACTIVE TEST


  1. DATA LIST

    Tech Tips

    Using the GTS to read the Data List allows the values or states of switches, sensors, actuators and other items to be read without removing any parts. This non-intrusive inspection can be very useful because intermittent conditions or signals may be discovered before parts or wiring is disturbed. Reading the Data List information early in troubleshooting is one way to save diagnostic time.

    Note

    In the table below, the values listed under "Normal Condition" are reference values. Do not depend solely on these reference values when deciding whether a part is faulty or not.


    1. Connect the GTS to the DLC3.

    2. Turn the ignition switch to ON.

    3. Turn the GTS on.

    4. Enter the following menus:


      • Body / Air Conditioner / Data List.

      • Powertrain / Engine and ECT / Data List.

    5. According to the display on the GTS, read the Data List.

      Air Conditioner
      Tester Display Measurement Item/Range Normal Condition Diagnostic Note
      Ambient Temp Sensor*

      Ambient temperature sensor /

      Min.: -23.3°C (-9.94°F)

      Max.: 65.95°C (150.71°F)

      Actual ambient temperature displayed

      Open in the circuit: -23.3°C (-9.94°F).

      Short in the circuit: 65.95°C (150.71°F).

      Adjusted Ambient Temp*

      Adjusted ambient temperature /

      Min.: -30.8°C (-23.44°F)

      Max.: 50.8°C (123.44°F)

      Adjusted ambient temperature displayed -
      Evaporator Fin Thermistor*

      No. 1 cooler thermistor /

      Min.: -29.7°C (-21.46°F)

      Max.: 59.55°C (139.19°F)

      Actual evaporator temperature displayed

      Open in the circuit: -29.7°C (-21.46°F).

      Short in the circuit: 59.55°C (139.19°F).

      Evaporator Target Temp*

      Target evaporator temperature /

      Min.: -327.68°C (-557.82°F)

      Max.: 327.67°C (621.81°F)

      Target evaporator temperature displayed -
      Engine Coolant Temp

      Engine coolant temperature /

      Min.: 1.3°C (34.34°F)

      Max.: 90.55°C (194.99°F)

      Actual engine coolant temperature displayed -
      Blower Motor Speed Level

      Blower motor speed level

      Min.: 0, Max.: 31

      Displayed speed level increases in range between 0 and 31 as blower motor speed increases -
      Regulator Pressure Sensor*

      Refrigerant pressure sensor /

      Min.: -0.4566 MPa

      Max.: 3.2943 MPa

      Actual refrigerant pressure displayed -
      Regulator Control Current

      Compressor assembly with pulley /

      0: Min., 0.997: Max.

      Value changes between 0 A and 0.997 A in accordance with compressor assembly with pulley operation -
      Air Mix Servo Targ Pulse (D)

      Air mix damper servo /

      5: Min., 92: Max. (for LHD)

      6: Min., 93: Max. (for RHD)

      for LHD:


      • 92 (pulse): Max cool

      • 5 (pulse): Max hot

      for RHD:


      • 6 (pulse): Max cool

      • 93 (pulse): Max hot

      -
      Air Mix Servo Actual Pulse (D)

      Air mix damper servo /

      5: Min., 92: Max. (for LHD)

      6: Min., 93: Max. (for RHD)

      for LHD:


      • 92 (pulse): Max cool

      • 5 (pulse): Max hot

      for RHD:


      • 6 (pulse): Max cool

      • 93 (pulse): Max hot

      -
      Air Outlet Servo Pulse (D)

      Air outlet damper servo /

      5: Min., 47: Max.

      47 (pulse): FACE

      37 (pulse): B/L

      17 (pulse): FOOT (M)

      17 (pulse): FOOT (A)

      9 (pulse): F/D

      5 (pulse): DEF

      -
      Air Outlet Servo Actual Pulse (D)

      Air outlet damper servo /

      5: Min., 47: Max.

      47 (pulse): FACE

      37 (pulse): B/L

      17 (pulse): FOOT (M)

      17 (pulse): FOOT (A)

      9 (pulse): F/D

      5 (pulse): DEF

      -
      Air Inlet Damper Targ Pulse

      Air inlet damper servo /

      7: Min., 19: Max. (for LHD)

      7: Min., 25: Max. (for RHD)

      for LHD:


      • 19 (pulse): Recirculation

      • 7 (pulse): Fresh

      for RHD:


      • 7 (pulse): Recirculation

      • 25 (pulse): Fresh

      -
      Air Inlet Damper Actual Pulse

      Air inlet damper servo /

      7: Min., 19: Max. (for LHD)

      7: Min., 25: Max. (for RHD)

      for LHD:


      • 19 (pulse): Recirculation

      • 7 (pulse): Fresh

      for RHD:


      • 7 (pulse): Recirculation

      • 25 (pulse): Fresh

      -
      Electric Heater Count

      Number of electric heaters operating /

      Min.: 0, Max.: 3

      - -
      Electric Heater Active Level

      Actual electric heater operation level /

      Min.: 0, Max.: 3

      Actual operation level of electric heater displayed -
      Refrigerant Shortage Check

      Refrigerant gas volume check /

      ON or OFF

      Customized value displayed -
      A/C Cutoff Signal The ECM sends the air conditioning control cut-off signal to the air conditioning amplifier assembly via CAN communication / OFF or ON

      OFF: The ECM does not send the air conditioning control cut-off signal

      ON: The ECM sends the air conditioning control cut-off signal

      -
      Refrigerant Gas Type

      Refrigerant gas type /

      R134a or 1234yf

      Refrigerant gas type displayed -
      Outside Air Mode Auto Switch Function

      Switches ON/OFF the function to switch the suction opening to the outside air mode automatically when the engine switch is turned off /

      OFF or ON

      Customized value displayed -
      Number of Trouble Codes

      Number of trouble codes /

      Min.: 0, Max.: 255

      Number of DTCs displayed -

      • *: w/ Cooler

      Engine and ECT
      Tester Display Measurement Item/Range Normal Condition Diagnostic Note
      A/C Signal* A/C signal / ON or OFF

      ON: A/C switch on

      OFF: A/C switch off

      -

      • *: w/ Cooler

  2. ACTIVE TEST

    Tech Tips

    Using the GTS to perform Active Tests allows relays, VSVs, actuators and other items to be operated without removing any parts. This non-intrusive functional inspection can be very useful because intermittent operation may be discovered before parts or wiring is disturbed. Performing Active Tests early in troubleshooting is one way to save diagnostic time. Data List information can be displayed while performing Active Tests.


    1. Connect the GTS to the DLC3.

    2. Turn the ignition switch to ON.

    3. Turn the GTS on.

    4. Enter the following menus: Body / Air Conditioner / Active Test.

    5. According to the display on the GTS, perform the Active Test.

      Air Conditioner
      Tester Display Test Part Control Range Diagnostic Note
      Blower Motor Blower with fan motor sub-assembly Min.: 0, Max.: 3 -
      Magnetic Clutch Relay* Magnet clutch relay operation ON or OFF Only item displayed (not supported)
      Defogger Relay (Rear) Rear window defogger relay operation ON or OFF -
      Heater Active Level Heater level Min.: 0, Max.: 3 -
      Air Mix Servo Targ Pulse (D) Driver side air mix servo motor pulse

      Min.: 5, Max.: 92 (for LHD)

      Min.: 6, Max.: 93 (for RHD)

      -
      Air Outlet Servo Pulse (D) Driver side air outlet servo motor pulse Min.: 5, Max.: 47 -
      Air Inlet Damper Targ Pulse Air inlet damper target pulse

      Min.: 7, Max.: 19 (for LHD)

      Min.: 7, Max.: 25 (for RHD)

      -

      • *: w/ Cooler