AIR CONDITIONING PRESSURE SENSOR REMOVAL


  1. RECOVER REFRIGERANT FROM AIR CONDITIONING SYSTEM


    1. Turn the power switch on (READY).

    2. Turn the A/C switch on.

    3. Operate the cooler compressor under the conditions shown below:

      Item Condition
      Engine Speed Idling
      Operating Time 3 minutes or more
      A/C Switch Status ON
      Blower Switch Status HI
      Set Temperature MAX COOL

      This cause most of the compressor oil from the various components of the A/C system to collect in the A/C compressor.

      Tech Tips

      It is not necessary to operate the cooler compressor if the A/C does not operate because of compressor lock etc.

    4. Turn the power switch off.

    5. Recover the refrigerant from the air conditioning system using a refrigerant recovery unit.

      Tech Tips

      Use the refrigerant recover unit in accordance with the manufacturer's instruction manual.

  2. REMOVE AIR CONDITIONER PRESSURE SENSOR


    1. Disconnect the connector.

    2. A01HT80

      Remove the air conditioner pressure sensor.

      Note

      Do not deform the piping.