AIR CONDITIONING SYSTEM DATA LIST / ACTIVE TEST


  1. DATA LIST

    Using the Techstream to read the Data List allows the values or states of switches, sensors, actuators and other items to be read without removing any parts. This non-intrusive inspection can be very useful because intermittent conditions or signals may be discovered before parts or wiring is disturbed. Reading the Data List information early in troubleshooting is one way to save diagnostic time.

    Note

    In the table below, the values listed under "Normal Condition" are reference values. Do not depend solely on these reference values when deciding whether a part is faulty or not.


    1. Connect the Techstream to the DLC3.

    2. Turn the power switch on (IG).

    3. Turn the Techstream on.

    4. Enter the following menus: Body Electrical / Air Conditioner / Data List.

    5. Check the value(s) by referring to the table below.

      Air Conditioner
      Tester Display Measurement Item/Range Normal Condition Diagnostic Note
      Room Temperature Sensor

      Room temperature sensor (cooler thermistor) /

      Min.: -6.50°C (20.30°F)

      Max.: 57.25°C (135.05°F)

      Actual cabin temperature displayed -
      Ambient Temp Sensor

      Ambient temperature sensor (thermistor assembly) /

      Min.: -23.30°C (-9.94°F)

      Max.: 65.95°C (150.71°F)

      Actual ambient temperature displayed -
      Adjusted Ambient Temp

      Adjusted ambient temperature /

      Min.: -30.80°C (-23.44°F)

      Max.: 50.80°C (123.44°F)

      - -
      Evaporator Fin Thermistor

      Evaporator temperature sensor (No. 1 cooler thermistor) /

      Min.: -29.70°C (-21.46°F)

      Max.: 59.55°C (139.19°F)

      Actual evaporator temperature displayed -
      Evaporator Target Temp

      Evaporator target temperature /

      Min.: -327.68°C (-557.82°F)

      Max.: 327.67°C (621.81°F)

      Evaporator target temperature displayed -
      Solar Sensor (D Side)

      Driver side automatic light control sensor (solar sensor) /

      Min.: 0

      Max.: 255

      Driver side automatic light control sensor (solar sensor) value increases as brightness increases -
      Solar Sensor (P Side)

      Front passenger side automatic light control sensor (solar sensor) /

      Min.: 0

      Max.: 255

      Front passenger side automatic light control sensor (solar sensor) value increases as brightness increases -
      Engine Coolant Temp

      Engine coolant temperature sensor /

      Min.: 1.30°C (34.34°F)

      Max.: 90.55°C (194.99°F)

      Actual engine coolant temperature displayed -
      Set Temperature (D Side)

      Driver side set temperature /

      Min.: MAX COLD

      Max.: MAX HOT

      Driver side set temperature displayed -
      Set Temperature (P Side)

      Front passenger side set temperature /

      Min.: MAX COLD

      Max.: MAX HOT

      Front passenger side set temperature displayed -
      Blower Motor Speed Level

      Blower motor speed level /

      Min.: 0

      Max.: 31

      Displayed speed level increases in range between 0 and 31 as blower motor speed increases -
      Regulator Pressure Sensor

      Air conditioning pressure sensor /

      Min.: -66.22 psi (gauge)

      Max.: 477.68 psi (gauge)

      Actual pressure displayed -
      Humidity Sensor

      Humidity sensor /

      Min.: 0%

      Max.: 100%

      Actual cabin humidity displayed -
      Air Mix Servo Targ Pulse(D)

      No. 2 air conditioning radiator damper servo sub-assembly (air mix*1) target pulse /

      Min.: 0

      Max.: 255

      MAX. COLD: 5 (pulse)

      MAX. HOT: 103 (pulse)

      -
      Air Mix Servo Actual Pulse(D)

      No. 2 air conditioning radiator damper servo sub-assembly (air mix*1) actual pulse /

      Min.: 0

      Max.: 255

      MAX. COLD: 5 (pulse)

      MAX. HOT: 103 (pulse)

      -
      Air Mix Servo Targ Pulse(P)

      No. 1 air conditioning radiator damper servo sub-assembly (air mix*2) target pulse /

      Min.: 0

      Max.: 255

      MAX. COLD: 105 (pulse)

      MAX. HOT: 7 (pulse)

      -
      Air Mix Servo Actual Pulse(P)

      No. 1 air conditioning radiator damper servo sub-assembly (air mix*2) actual pulse /

      Min.: 0

      Max.: 255

      MAX. COLD: 105 (pulse)

      MAX. HOT: 7 (pulse)

      -
      Air Outlet Servo Pulse (D)

      No. 1 air conditioning radiator damper servo sub-assembly (air outlet) target pulse /

      Min.: 0

      Max.: 255

      FACE: 8 (pulse)

      B/L: 30 (pulse)

      FOOT (Manual mode) : 67 (pulse)

      FOOT (Automatic mode) : 60, 67 or 74 (pulse)

      FOOT/DEF: 80 (pulse)

      DEF: 97 (pulse)

      -
      Air Outlet Servo Actu Pulse(D)

      No. 1 air conditioning radiator damper servo sub-assembly (air outlet) actual pulse /

      Min.: 0

      Max.: 255

      FACE: 8 (pulse)

      B/L: 30 (pulse)

      FOOT (Manual mode) : 67 (pulse)

      FOOT (Automatic mode) : 60, 67 or 74 (pulse)

      FOOT/DEF: 80 (pulse)

      DEF: 97 (pulse)

      -
      Air Inlet Damper Targ Pulse

      No. 1 blower damper servo sub-assembly (air inlet) target pulse /

      Min.: 0

      Max.: 255

      RECIRCULATION: 7 (pulse)

      FRESH: 28 (pulse)

      -
      Air Inlet Damper Actual Pulse

      No. 1 blower damper servo sub-assembly (air inlet) actual pulse /

      Min.: 0

      Max.: 255

      RECIRCULATION: 7 (pulse)

      FRESH: 28 (pulse)

      -
      Electric Heater Count

      Maximum heater operation level /

      Min.: 0

      Max.: 2

      Maximum possible operation level of quick heater assembly displayed -
      Electric Heater Active Level

      Actual heater operation level /

      Min.: 0

      Max.: 2

      Actual operation level of quick heater assembly displayed -
      Compressor Speed

      Compressor speed /

      Min.: 0 rpm

      Max.: 65535 rpm

      Actual compressor rotation speed displayed -
      Compressor Target Speed

      Compressor target speed /

      Min.: 0 rpm

      Max.: 65535 rpm

      Compressor target rotation speed displayed -
      Shift Set Temperature

      Shift set temperature /

      2C decr, 1C decr, Normal, 1C incr, 2C incr

      Customized value displayed -
      Air Inlet Mode

      Air inlet mode /

      Auto or Manual

      Customized value displayed -
      Compressor Mode

      Compressor mode /

      Auto or Manual

      Customized value displayed -
      Noise and Vibration Reduction

      Noise and vibration reduction /

      OFF or ON

      Customized value displayed -
      ECO MODE Cancel

      ECO MODE Cancel /

      OFF or ON

      Customized value displayed -
      ECO Switch

      ECO mode switch (eco switch assembly) /

      OFF or ON

      ECO mode switch (eco switch assembly) operated: ON

      (when switch is pressed)

      -

      ECO mode switch (eco switch assembly) not operated: OFF

      (when switch is not pressed)

      -
      Refrigerant Shortage Check

      Refrigerant shortage check /

      ON or OFF

      Customized value displayed -
      Fan speed increment control

      Fan speed increment control /

      Slow, Normal, Fast

      Customized value displayed -
      Foot/DEF Auto Mode

      Foot/DEF Auto Mode /

      ON or OFF

      Customized value displayed -
      Foot/DEF Auto Blow Up

      Foot/DEF Auto blower speed increase /

      ON or OFF

      Customized value displayed -
      Ambient Temperature Shift

      Ambient temperature shift /

      3C decr, 2C decr, 1C decr, Normal, 1C incr, 2C incr, 3C incr

      Customized value displayed -
      Pls Servo Test Sts

      Pulse servo motor test status/

      Wait, Move, Comp, Error, Stop

      Pulse servo motor test status -
      Compressor Drive Check

      Compressor drive check /

      OK or NG

      NG: Compressor does not drive

      OK: Compressor drives

      -
      Glass Temperature

      Glass temperature /

      Min.: -327.68°C (-557.82°F)

      Max.: 327.67°C (621.81°F)

      Actual glass temperature displayed -
      Glass Surroundings Temperature

      Glass surroundings temperature /

      Min.: -327.68°C (-557.82°F)

      Max.: 327.67°C (621.81°F)

      Actual glass surroundings temperature displayed -
      Outside Air Mode Auto Switch Function

      Outside air mode auto switch function /

      ON or OFF

      Customized value displayed -
      Number of Trouble Codes

      Number of trouble codes /

      Min.: 0

      Max.: 255

      Number of DTCs displayed -

      • *1: for Driver Side

      • *2: for Front Passenger Side

  2. ACTIVE TEST

    Using the Techstream to perform Active Tests allows relays, VSVs, actuators and other items to be operated without removing any parts. This non-intrusive functional inspection can be very useful because intermittent operation may be discovered before parts or wiring is disturbed. Performing Active Tests early in troubleshooting is one way to save diagnostic time. Data List information can be displayed while performing Active Tests.


    1. Connect the Techstream to the DLC3.

    2. Turn the power switch on (IG).

    3. Turn the Techstream on.

    4. Enter the following menus: Body Electrical / Air Conditioner / Active Test.

    5. Check the operation by referring to the table below.

      Air Conditioner
      Tester Display Test Part Control Range Diagnostic Note
      Blower Motor Blower motor with fan sub-assembly Min.: 0, Max.: 31 -
      Compressor Target Speed Compressor with motor assembly Min.: 0, Max.: 7500 -
      Defogger Relay (Rear) Defogger relay (engine room junction block assembly) OFF, ON -
      Water Pump Engine water pump assembly OFF, ON -
      Heater Active Level Quick heater assembly Min.: 0, Max.: 2 -
      Air Mix Servo Targ Pulse(D) No. 2 air conditioning radiator damper servo sub-assembly (air mix*1) pulse Min.: 0, Max.: 255 Operates between 5 and 103 pulses
      Air Mix Servo Targ Pulse(P) No. 1 air conditioning radiator damper servo sub-assembly (air mix*2) pulse Min.: 0, Max.: 255 Operates between 7 and 105 pulses
      Air Outlet Servo Pulse (D) No. 1 air conditioning radiator damper servo sub-assembly (air outlet) pulse Min.: 0, Max.: 255 Operates between 8 and 97 pulses
      Air Inlet Damper Targ Pulse No. 1 blower damper servo sub-assembly (air inlet) pulse Min.: 0, Max.: 255 Operates between 7 and 28 pulses

      • *1: for Driver Side

      • *2: for Front Passenger Side