INSPECT REFRIGERANT VOLUME
| *1 | Sight Glass |
Check the sight glass on the cooler refrigerant liquid pipe A.
Test conditions:
Temperature at the air inlet is 30 to 35°C (86 to 95°F).
Engine is running at 1500 rpm.
Blower speed control switch is at HI.
A/C switch is ON.
Temperature control switch is at the MAX. COOL position.
Doors are fully open.
| Item | Symptom | Amount of Refrigerant | Corrective Procedures |
|---|---|---|---|
| 1 | Bubbles visible | Insufficient* | (1) Check for gas leakage and repair if necessary (2) Add refrigerant until bubbles disappear |
| 2 | No bubbles visible | Empty, insufficient or too much | Refer to items 3 and 4 |
| 3 | No temperature difference between compressor inlet and outlet | Empty or nearly empty | (1) Check for gas leakage with halogen gas leak detector and repair if necessary (2) Add refrigerant until bubbles disappear |
| 4 | Considerable temperature difference between compressor inlet and outlet | Correct or too much | Refer to items 5 and 6 |
| 5 | Immediately after air conditioning is turned OFF, refrigerant becomes clear | Too much | (1) Drain or discharge refrigerant (2) Bleed air and supply proper amount of purified refrigerant |
| 6 | Immediately after air conditioning is turned OFF, refrigerant foams and then becomes clear | Correct | - |
Tech Tips
*: If the ambient temperature is higher than usual but cooling is sufficient, bubbles in the sight glass are permissible.
INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET
This method uses a manifold gauge set to locate problem areas. Read the manifold gauge pressure when these conditions are established.
Test conditions:
Temperature at the air inlet is 30 to 35°C (86 to 95°F).
Engine is running at 1500 rpm.
All doors are fully open.
Blower speed control switch is at HI.
A/C switch is ON.
Gauge readings (Reference).
| *a | Pressure on low-pressure side | *b | Blower HI zone |
| *c | Blower LO zone (MPa (kgf/cm2, psi)) |
*d | Pressure on high-pressure side (MPa (kgf/cm2, psi)) |
Normally functioning refrigeration system
| Gauge Reading | ||||||
|---|---|---|---|---|---|---|
|
The air conditioning system periodically changes between normal and improper function due to moisture in the refrigerant system.
| Symptom | Probable Cause | Diagnosis | Corrective Actions |
|---|---|---|---|
| During operation, pressure on low pressure side cycles between normal and vacuum | Moisture in refrigeration system freezes at expansion valve orifice, causing temporary stop of cycle. However, when melted, normal state is restored. |
|
|
The air conditioning system does not function effectively due to insufficient cooling.
| Symptom | Probable Cause | Diagnosis | Corrective Actions |
|---|---|---|---|
|
Gas leakage from refrigeration system |
|
|
The air conditioning system does not function effectively due to poor circulation of the refrigerant.
| Symptom | Probable Cause | Diagnosis | Corrective Actions |
|---|---|---|---|
|
Refrigerant flow obstructed by dirt in condenser | Condenser clogged | Replace condenser |
The air conditioning system does not function or functions intermittently because the refrigerant does not circulate.
| Symptom | Probable Cause | Diagnosis | Corrective Actions |
|---|---|---|---|
|
|
Refrigerant does not circulate |
|
The air conditioning system does not function effectively due to overcharged refrigerant or insufficient cooling of the condenser.
| Symptom | Probable Cause | Diagnosis | Corrective Actions |
|---|---|---|---|
| Pressure extremely high on both low and high-pressure sides |
|
|
|
The air conditioning system does not function due to air in the refrigeration system.
CAUTION:
The low-pressure piping may be very hot and cause serious burns.
Note
These gauge indications occur when the refrigeration system opens and the system is charged with refrigerant without vacuum purging.
| Symptom | Probable Cause | Diagnosis | Corrective Actions |
|---|---|---|---|
|
Air in refrigeration system |
|
|
The air conditioning system does not function effectively due to an expansion valve malfunction.
| Symptom | Probable Cause | Diagnosis | Corrective Actions |
|---|---|---|---|
|
Problem with expansion valve |
|
Replace expansion valve |
The air conditioning system does not function due to a defective compressor.
| Symptom | Probable Cause | Diagnosis | Corrective Actions |
|---|---|---|---|
|
Internal leakage in compressor |
|
Repair or replace compressor |