AMBIENT TEMPERATURE SENSOR INSPECTION


  1. INSPECT AMBIENT TEMPERATURE SENSOR


    1. A01BFL8E04

      Remove the ambient temperature sensor.

    2. Disconnect the connector from the ambient temperature sensor.

    3. Measure the resistance according to the value(s) in the table below.

      Standard resistance
      Tester Connection Condition Specified Condition
      1 - 2 10°C (50°F) 3.00 to 3.73 kΩ
      1 - 2 15°C (59°F) 2.45 to 2.88 kΩ
      1 - 2 20°C (68°F) 1.95 to 2.30 kΩ
      1 - 2 25°C (77°F) 1.60 to 1.80 kΩ
      1 - 2 30°C (86°F) 1.28 to 1.47 kΩ
      1 - 2 35°C (95°F) 1.00 to 1.22 kΩ
      1 - 2 40°C (104°F) 0.80 to 1.00 kΩ
      1 - 2 45°C (113°F) 0.65 to 0.85 kΩ
      1 - 2 50°C (122°F) 0.50 to 0.70 kΩ
      1 - 2 55°C (131°F) 0.44 to 0.60 kΩ
      1 - 2 60°C (140°F) 0.36 to 0.50 kΩ

      Note


      • Even slightly touching the sensor may change the resistance value. Be sure to hold the connector of the sensor.

      • When measuring, the sensor temperature must be the same as the ambient temperature.

      Tech Tips

      As the temperature increases, the resistance decreases (see the graph).

      If the operation is not as specified, replace the ambient temperature sensor.